DWB03, PWB03

Function/Range/Level/Time Setting

Select the desired func-

tion setting the DIP-switch-

es 1 to 4 as shown on the 

right. Adjust the input range 

setting the DIP-switch-

es 5 and 6. To access the 

DIP-switches open the plas-

tic cover using a screwdriver 

as shown below.

If DIP switch 3 is set to ON 

(start/stop) the position 

of DIP switch 4 does not 

affect the products’ working 

mode.

Center knobs:

Setting of upper and lower-

level from -100 to 100% of 

nominal power.

Lower left knob:

Setting of delay on absolute 

scale: 0.1 to 30 s.

Lower right knob:

Setting of power ON delay 

on absolute scale: 1 to 30 s.

Measuring range

SW5 ON  ON  OFF  OFF
SW6 

ON OFF ON  OFF

M23 

208 VAC  220 VAC  230 VAC 

240 VAC

M48 

380 VAC  400 VAC  415 VAC 

480 VAC

     

DWB03 

only

M69 

600 VAC  690 VAC  600 VAC 

690 VAC

Contact input (SW3 OFF)

ON:  Latch function enable

OFF:  Inhibit function enable

Working mode

ON:  Contact input for start/stop functions

OFF:  Contact input for latch/inhibit functions

Input current range (terminals I1, I2 or 10, 11)

ON: 10A

OFF: 5A/MI

Relay status

ON:  Relay de-energized in normal condition

OFF:  Relay energized in normal condition

Contact input working mode

 

                  

CLOSED

  

 

 

OPEN

LATCH

                   NOT ACTIVE 

 

ACTIVE

INHIBIT

                   ACTIVE                  NOT ACTIVE

START/STOP

             START   

 

  STOP

Contact input

DWB03

Contact input

PWB03

Notes

1.

 DIP-switch 3 set ON enables the start/stop function 

  that is managed by the closing-opening of the con- 

  tact input.

2.

 DIP-switch 3 set OFF enables the input contact for  

  the latch/inhibit functions: the selection between 

 

  these is allowed by DIP switch 4.

The following table shows as the input contact man-

ages the mode of operation:

Mode of Operation (cont.)

the output relay releas-

es and the red LED turns 

on after the set time has 

expired. When the start/stop 

contact is opened the relay 

is immediately de-energized. 

To restart the system just 

connect the start/stop con-

tact.

Note 1:

 to use the start/stop 

function the output relay has 

to command a contactor in 

series to the load (see last 

two wiring diagrams).

Note 2

 (3-phase voltage): 

connect the 3-phase power 

supply to the terminals L1, 

L2 and L3 (DWB03) - 5, 6 

and 7 (PWB03) taking care 

of the sequence.