2

Specifications are subject to change without notice (16.10.08)

DWB02, PWB02

Supply Specifications

General Specifications

Power supply

Overvoltage cat. III

Rated operational voltage

(IEC 60664, IEC 60038)

Through terminals:

DWB02:

L1, L2, L3

PWB02:

5, 6, 7

M23

177 to 276 VAC 45 to 65 Hz

DWB02CM48

323 to 552 VAC 45 to 65 Hz

PWB02CM48

323 to 477 VAC 45 to 65 Hz

DWB02CM69

510 to 793 VAC 45 to 65 Hz

Dielectric voltage supply to output

4 kV

Rated operational power

M23

9 VA @ 230 V, 50 Hz

M48

13 VA @ 400 V, 50 Hz

M69

21 VA @ 600 V, 50 Hz

Supplied by L1 and L2

Power ON delay

1 to 30 s ± 0.5 s

Reaction time

(input signal variation from
-20% to +20% or from
+20% to -20% of set value)

Alarm ON delay

< 250 ms

Alarm OFF delay

< 250 ms

Accuracy

(15 min warm-up time)

Temperature drift

± 1000 ppm/°C

Delay ON alarm

± 10% on set value ± 50 ms

Repeatability

± 0.5% on full-scale

Indication for

Power supply ON

LED, green

Alarm ON

LED, red (flashing 2 Hz
during delay time)

Output relay ON

LED, yellow

Environment

Degree of protection

IP 20

Pollution degree 

3 (DWB02), 2 (PWB02)

Operating temperature

@ Max. voltage, 50 Hz

-20 to +60°C, R.H. < 95%

@ Max. voltage, 60 Hz

-20 to +50°C, R.H. < 95%

Storage temperature

-30 to +80°C, R.H. < 95%

Housing 

Dimensions

DWB02

45 x 80 x 99.5 mm

PWB02

36 x 80 x 94 mm

Weight

Approx. 250 g

Screw terminals

Tightening torque

Max. 0.5 Nm
acc. to IEC 60947

Approvals

UL, CSA

CE-Marking

Yes

EMC

Electromagnetic Compatibility

Immunity

According to EN 61000-6-2

Emission

According to EN 61000-6-3

Mode of Operation

DWB02 and PWB02 mea-
sure the active power of a 3-
phase balanced system. The
relay has an adjustable pow-
er ON delay in order to avoid
undesired overload detec-
tion during motor start.

Example 1

Latching mode, relay NE
In this application DWB02 or
PWB02 is connected to an
external current metering
transformer, type MI..., (con-
nected between U1 & U2) as
well as to a 3-phase asyn-
chronous motor. The relay is
energized as soon as the
power supply is applied.
After the power ON delay,
the unit starts to measure
power. If it is within the set-
points, the relay is ener-

gized, and the yellow LED is
ON. As soon as the power
drops below the lower set-
point or raises above the
upper setpoint the output
relay releases after the set
time has expired. To restart
the measurement, connect
Z1 and U1 (2 and 9) or inter-
rupt the power supply for at
least 1 s.

Example 2

Non-latching mode, relay
NE.
DWB02 and PWB02 react
as described in the previous
example 1 except that the
relay reactivates automati-
cally as soon as active pow-
er is back within the two
setpoints again. When the
measured power rises

above the adjusted upper
level, the red LED starts
flashing, and the output
relay releases after the set
time period. When the mea-
sured power drops below
the adjusted lower level, the
red LED starts flashing, and
the output relay releases
after the set time period.

Example 3:

DWB02CM2310A and
PWB02CM2310A can be
used for monitoring the
power of a 1-Phase load
with 208 to 240 V AC mains
voltage. In this case the
power supply has to be con-
nected between L1, L2 (or 5,
6); L2 and L3 (or 6 and 7)
have to be interconnected.

Example 4

Start/stop mode, relay NE.
In this application DWB02 or
PWB02 are directly connect-
ed to a 3-phase asyn-
chronous motor. The relay is
energized as soon as the
power supply is applied and
the start/stop contact is
closed. After the power ON
delay, the unit starts to mea-
sure the active power. If it is
within the setpoints the relay
is energized. As soon as the
power drops below the low-
er setpoint or raises above
the upper setpoint the out-
put relay releases and the
red LED turns on after the
set time has expired. When
the start/stop contact is
opened the relay is immedi-
ately de-energized. To

Output Specifications

Output

SPDT relay

Rated insulation voltage

250 VAC

Contact ratings

(AgSnO

2

)

µ

Resistive loads

AC 1

8 A @ 250 VAC

DC 12

5 A @ 24 VDC

Small inductive loads AC 15

2.5 A @ 250 VAC

DC 13

2.5 A @ 24 VDC

Mechanical life

30 x 10

6

operations

Electrical life

10

5

operations

(at 8 A, 250 V, cos 

ϕ

= 1)

Operating frequency

7200 operations/h

Dielectric strength

Dielectric voltage

2 kVAC (rms)

Rated impulse withstand volt. 4 kV (1.2/50 µs)

Summary of Contents for DWB02

Page 1: ...e alarm condition Inhibit func tion can be used to avoid relay operation when not desired maintenance tran sitions The LED s indicate the state of the alarm and the output relay Input Specifications Input Voltage Own power supply 3 phase DWB02 L1 L2 L3 PWB02 5 6 7 M23 208 to 240 VAC 15 DWB02CM48 380 to 480 VAC 15 PWB02CM48 380 to 415 VAC 15 DWB02CM69 600 to 690 VAC 15 1 phase DWB02CM23 L1 L2 PWB02...

Page 2: ...arts to measure power If it is within the set points the relay is ener gized and the yellow LED is ON As soon as the power drops below the lower set point or raises above the upper setpoint the output relay releases after the set time has expired To restart the measurement connect Z1 and U1 2 and 9 or inter rupt the power supply for at least 1 s Example 2 Non latching mode relay NE DWB02 and PWB02...

Page 3: ...able Working mode ON Contact input for start stop functions OFF Contact input for latch inhibit functions Input current range terminals I1 I2 or 10 11 ON 10A OFF 5A MI Relay status ON Relay de energized in normal condition OFF Relay energized in normal condition Contact input working mode CLOSED OPEN LATCH NOT ACTIVE ACTIVE INHIBIT ACTIVE NOT ACTIVE START STOP START STOP Mode of Operation cont res...

Page 4: ...ower ON Power ON Power ON Lower level Relay ON Power supply Inhibit contact Closed inhibit active Upper level Hysteresis Hysteresis Active power Lower level Relay ON Wiring Diagrams DWB02 Direct connection PWB02 Direct connection Latch Inhibit Contact Latch Inhibit Contact T T Start and stop function NE relay Power ON Power supply Start Stop contact Closed Start Open Stop Upper level Hysteresis Hy...

Page 5: ...ibit Contact L2 L3 L1 m 15 16 18 L1 L2 L3 U1 U2 Z1 I2 I1 I1 N P P 6 7 5 m 1 4 3 L1 L2 L3 9 8 2 10 11 I1 N P P PWB02 Direct connection Manual start and stop NE relay DWB02 Direct connection Manual start and stop NE relay Start stop Contact Start stop Contact Wiring Diagrams cont With the start stop function enabled it s necessary to use the following wiring diagrams which are two examples among man...

Page 6: ...6 Specifications are subject to change without notice 16 10 08 DWB02 PWB02 45 80 83 5 99 5 63 28 5 36 80 94 28 5 63 90 Dimensions DIN rail Plug in ...

Reviews: