Mode of operation

LEDs

Status

Description

Green

)

ON

Power supply ON

OFF

Power supply OFF

Red
(AL)

ON (steady)

Alarm situation is still present at the end of delay

OFF

Alarm OFF

Flashing 2 Hz

Under or overvoltage alarm triggered with a delay on alarm elapsing

Flashing 5 Hz

Phase loss or incorrect phase sequence alarm

Yellow

)

ON

Relay output energised

OFF

Relay output de-energised

Phase loss alarm

Input variables

L1-L2, L2-L3 and L3-L1

Alarm setpoint

One phase ≤ 85% of the rated value (regenerated voltage detection)

Restore setpoint All phases > 85% of the rated value + Hysteresis

Reaction time

≤ 200 ms

Hysteresis

2% fixed

Delay ON

None

Delay OFF

None

Phase sequence alarm

Input variables Connection L1, L2, L3

Reaction time

≤ 200 ms

Delay ON

None

Delay OFF

None

Over / under voltage alarms

Input variables

3P: voltages V

L12

, V

L23

, V

L31

3P+N: voltages V

L1N

, V

L2N

, V

L3N

Reaction time

≤ 200 ms + set delay ON alarm

Undervoltage setting range From -2 to -22%

Overvoltage setting range

From 2 to 22%

Repeatability

1% r 1 V

Hysteresis

Setpoint between 2% and 5% → Hys 1%

Setpoint between 5% and 22% → Hys 2%

Instruction manual_DPB01, PPB01 | 06/12/2022 | Copyright © 2022 CARLO GAVAZZI Controls SpA

5

Summary of Contents for DPB01

Page 1: ...DPB01 PPB01 Instruction manual Version 06 12 2022...

Page 2: ...l when present B Information LEDs l Yellow for relay output status l Red for signal alarm status l Green for device ON C DIP switches setting the nominal voltage type of mains power ON delay D Output...

Page 3: ...ect the relay output according to the ratings For DIN rail versions automatic screwdriver can be used with maximum tightening torque 0 5 Nm Keep power OFF while connecting Terminals Power supply DPB01...

Page 4: ...point Overvoltage adjustment dial Typology Linear selection from 2 to 22 Resolution 2 setpoint increase per notch Function Relative undervoltage setpoint Set the desired delay on alarm if required by...

Page 5: ...ue regenerated voltage detection Restore setpoint All phases 85 of the rated value Hysteresis Reaction time 200 ms Hysteresis 2 fixed Delay ON None Delay OFF None Phase sequence alarm Input variables...

Page 6: ...ZI Controls SpA Over under voltage alarms Delay ON Adjustable from 0 1 to 30 s Accuracy from 50 ms at 0 1 s to 5 s at 30 s Repeatability from 10 ms at 0 1 s to 1 s at 30 s Delay OFF None Operating dia...

Page 7: ...DIN rail Hang the device to the DIN rail being sure that the spring closes Use a screwdriver to remove the product as shown in figure Instruction manual_DPB01 PPB01 06 12 2022 Copyright 2022 CARLO GAV...

Page 8: ...or modules shall be carried out by qualified personnel and after having disconnected all power sources A readily accessible overcurrent protection fuse or circuit breaker shall be incorporated in the...

Reviews: