Carlin EZ-Temp 90300 Datasheet Download Page 3

MN90300B  072016

Model 90300 Microprocessor Temperature Controls — Data sheet

Mounting – 

90300 controls mount to any standard well. Mount 

the 90300 directly to a well (new or existing) with hardware 

supplied in the separate well mounting kit. See below for 

dimensions. 

Well Kits – 

Wells for 90300 sensors are available in the sizes shown 

below. Well kits include sensor mounting hardware designed to 

hold sensor securely in position. 

Sensors – 

Sensors are available separately for 90300 only. 

Configurations

Error Codes

3"

4

3

/

8

"

4

3

/

4

"

Error Code

Reason

01

Primary (K2) relay is welded on. 

Note: 

If the control is reset 

from error code 01, the red LED will flash every 5 seconds 

indicating the control must be replaced.

02

Primary & Safety relays (K1 and K2) on. The control cannot 

be reset from error code 02 and must be replaced.

03

Primary & Safety relays (K1 and K2) are off

05

Simulated High Temp lockout

06

Temp is above set high temp but below thermistor high 

(250°F)

16

AC line frequency out of tolerance

Error Code

Reason

20

Temp sensor 1 out of range failure

21

Temp sensor 2 out of range failure

22

High limit temp sensor out of range failure

23

Temp sensor 1 pin is open

24

Temp sensor 2 pin is open

25

High limit temp sensor is open

07

,

 10

,

  1 1

,

 12

,

 13

,

 14

,

 15

Internal hardware safety failure – unit should be replaced. Contact customer service for additional informa-

tion. 1-800-989-2275

Reviews: