Carlin 601GAS Instruction Manual Download Page 6

Model 601GAS burner — Instruction manual

MN601GAS  012516

– 6 –

Where appliance instructions differ from this manual, follow the appliance instructions.

1.  Prepare site   •   prepare burner   •   mount burner

Vent system

Inspect, repair and/or replace vent system

  Do not install this burner unless you have verified the entire 

vent system and the appliance are in good condition and 

comply with all applicable codes. And . . .

 

The vent and chimney must be sized and constructed in 

accordance with all applicable codes. If intended for use 

with an oil burner as well, the vent system must comply 

with relevant codes for both gas and oil firing.

 

The vent system must not be pressurized unless the vent 

piping and vent system are designed accordingly. The vent 

must provide draft at all times (negative pressure in vent).

 

Do not install or use an existing manual damper in the vent 

connector or vent.

 

Do not connect the appliance vent connector to a chimney 

or vent serving a fireplace, incinerator or solid-fuel-burning 

apparatus.

 

In a cold climate, do not vent into a masonry chimney 

that has one or more sides exposed to the outside. 

Install a listed stainless steel liner to vent the flue 

products.

 

A defective vent system could result in severe personal 

injury, death or substantial property damage.

Vent/chimney sizing

•  Follow all local codes when sizing the vent and chimney

.

•  Refer to the appliance manufacturer’s manual, when available, for venting 

recommendations.

Prepare vent/chimney

•  Secure all metal vent joints with screws, following the vent manufacturer’s 

instructions. Seal all joints in the vent system and chimney. Repair ma-

sonry chimney lining and repair all mortar joints as needed.

•  Per ANSI Z21.8, install a double-acting barometric draft regulator in the 

vent piping. (The damper must be located in the same space as the 

appliance.) Install a manual reset spill switch on the draft regulator per 

instructions. Wire the switch into the appliance limit circuit to shut off the 

appliance/burner if sustained downdraft should occur. Refer to the appli-

ance manufacturer’s instruction manual for recommendations regarding 

the need for a barometric draft regulator.

•  Provide support for the vent piping. Do not rest the weight of any of the 

vent piping on the appliance flue outlet.

Figure 1

 

Vent and vent connector installations, typical

Summary of Contents for 601GAS

Page 1: ...pply pressure 5 inches w c Manifold pressure 3 5 inches w c Electrical Power 120V 60 Hz 1 Phase Motor Marathon PSC 1 2 HP 3450 RPM 8 4 amps Total Current Approx less than 10 amps Ignition Carlin Model...

Page 2: ...Model 601GAS burner Instruction manual MN601GAS 012516 2 Where appliance instructions differ from this manual follow the appliance instructions...

Page 3: ...husetts require a nonre cycle primary control and gas train Make sure the burner is properly equipped for Massachusetts installations United States installations Burner appliance installations in the...

Page 4: ...d burner flange door for access and removal of combustion head gas manifold assembly 10 Ignitor Carlin Model 41000 solid state electronic ignitor 14 000 volts continuous duty rated 11 Hinged cover pla...

Page 5: ...01GAS 012516 5 Where appliance instructions differ from this manual follow the appliance instructions 601GAS burner at a glance ITEM 17 MassachusettsCodeburnersalsoinclude an 8 second time delay relay...

Page 6: ...hat has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe personal injury death or substantial pr...

Page 7: ...tion manual when available to size combustion air openings Use the following guidelines when appliance instructions are not available All air from inside building building must be well ventilated Size...

Page 8: ...s chamber liners may contain carcinogenic particles chrystobalites after exposure to heat Airborne particles from fiberglass or ceramic fiber components have been listed as potentially carcinogenic by...

Page 9: ...NA 31 32 9687 21 32 6562 5 5 1 350 000 NA NA NA NA NA NA 1 1 000 11 16 6875 6 1 400 000 NA NA NA NA NA NA 1 1 16 1 063 23 32 7187 6 5 1 450 000 NA NA NA NA NA NA 1 1 8 1 125 3 4 7500 8 75 1 500 000 N...

Page 10: ...ir tube insertion length Btuh L W C L H VC Dry Wet Dry Wet Dry Wet Wet Dry Wet 700 000 18 22 16 18 7 5 8 5 19 16 22 Welded flange Burners with welded flange have fixed usable tube length UTL set for t...

Page 11: ...proceeding b Close the manual gas valve on the gas supply line c Disconnect the burner gas train union d Remove the gas pipe at the burner air tube e Remove the four nuts securing the burner hinged do...

Page 12: ...in J box b See the label in the burner junction box or the wiring diagram on page 15 Gas valve vent opening If local codes require install piping from vent connection to outside sized and installed pe...

Page 13: ...y pressure 5 inches w c Do not expose the gas train to gas pressure in excess of 14 inches water column Higher pressure could damage the valve seat resulting in potentially hazardous condition When pr...

Page 14: ...roximately Approximate amp draw Motor 1 2 HP During ignition Add 0 5 amps to steady current below Steady operation Carlin motor 5 2 AMPS Marathon motor 8 4 amps 2 The 120 vac power connections to the...

Page 15: ...nstructions differ from this manual follow the appliance instructions Figure 11 Wiring diagrams 601GAS burner with 60200FR primary control typical Standard Commercial Gas Train 120V Ventless Commercia...

Page 16: ...joints near burner and check for any leaks If any leaks appear repair before proceeding and retest Set burner air damper See Figure 12 Loosen air damper locking nut Then rotate the ajustment screw un...

Page 17: ...eset control from Latch up Press for 30 second Display Control ESC Display previous Operating State from Operating screen Exit Log or Setup screen to Operating screen with 3 second press Scroll throug...

Page 18: ...n TFI or Post purge Motor ignitor or valve relay weld detected If the control is miswired causing voltage to be detected on the outputs terminals motor ignitor or valve when not ex pected Recycle limi...

Page 19: ...urrent causes the cycle to be faulted Recycle Yes if a recycle occurred in CFH cycle A recycle causes the cycle to be faulted No Run time Time motor output is on during this cycle Burn time Time valve...

Page 20: ...ac Check all electrical connections Control is in lockout Press the reset button for 1 second Other no start problems Line voltage 90 VAC Check line voltage 132VAC Motor relay welded If valve ignitor...

Page 21: ...per appliance instruction manual Burner components settings verified against Table 1a page 9 Burner appliance installed per all applicable codes Installation site has adequate ventilation openings and...

Page 22: ...the manifold gas pressure with the manometer Set the high gas pressure switch to a pressure less than actual manifold pressure The high gas pressure switch should shut the burner down Replace the swi...

Page 23: ...erform the complete checkout procedures of pages 16 through 22 including system inspection and checks 6 Maintenance and service procedures Maintenance service procedures Cleaning blower wheel 1 The bl...

Page 24: ...e door is closed securely and that door switch is closed Gas pressure Check low gas pressure switch If it is open gas supply may be too low or no gas flow check supply line and manual valves Gas train...

Page 25: ...ifice size Check gas orifice size See Table 1a page 9 Manifold pressure Check gas manifold pressure should be between 3 2 and 3 8 inches w c unless specified Low gas supply pressure Check line pressur...

Page 26: ...9147 99427 9a Static disc Built into 1x and 2x heads non removable not used in 3x heads NA 9b Diffuser plate 1x heads only 99162 Combustion head assemblies 11 combustion head assembly includes items s...

Page 27: ...follow the appliance instructions 8 Replacement parts Burner continued Set screws Combustion head assembly Burnerisshownwithweldedflange suppliedonlyonburners ordered for specific appliance applicatio...

Page 28: ...surized firing Failure to comply could result in severe personal injury death or substantial property damage When using a welded flange burner verify the insertion depth on the appliance and burner se...

Page 29: ...Model 601GAS burner Instruction manual MN601GAS 012516 29 Where appliance instructions differ from this manual follow the appliance instructions...

Page 30: ...model Serial number Measured firing rate Btuh Gas orifice drill size Manifold gas pressure IWC Inlet gas pressure IWC r p r o l a r u t a n l e u F 2 O 2 O C opane Were controls tested Comments about...

Reviews: