12
“manuale thT” +0300077IE - rel. 1.3 - 11.04.2016
ENG
LCD
display
Description
Default
value
Note
PS
Password
00
Password is: 22
FH
FAN/HEATING confi guration
00
• 00:FAN
• 01:HEATING
Co
Confi guration “mode” button
3
see table in the bottom
tC
Temperature sensor
calibration
0.0 °C
-5.0 to 5.0 °C
HC
Humidity sensor calibration
0.0% rH
-10.0% to 10.0% rH
FE
Enable frost protection mode
01
• 00:Disable
• 01:Enable
Ft
Frost protection set point
5.0 °C
5 to 17 °C
Id
BMS address
50
50 to 81
br
Baud rate
00
• 00:19200
• 01:9600
• 02:4800
bE
Buzzer Enable
01
• 00:Disable
• 01:Enable
dF
Diff erential
0.5 °C
• 0.5 °C
• 1.0 °C
• 1.5 °C
• 2.0 °C
LE
Key Lock Enable
0
• 00:Disable
• 01:Enable
rC
Relay management
00
• 00:Automayic
• 01:Manual
Ar
Auto recovery
01
fi xed
tE
Confi guration clock button
07
01 to 07
tM
ON/OFF button by
00
• 00:Thermostat
• 01:RS485
IE
Number of variables to show
on display
00
00 to 05
dS
Mode button by
00
• 00:Thermostat
• 01:Modbus
FS
FAN/HEATING button by
00
• 00:Thermostat
• 01:Modbus
Keypad
F
unctionalities
Key Mode
To select the sequence of icons to show on display, enter in the
Parameters Menù and confi gure the parameter “Co“ and with rotary
encoder select the new value turning right or left, then press
to
confi rm. Here below, possible symbols to manage are:
the symbols can be turn on separately or in pairs and the sequence is
defi ned setting to “1“ the diff erent bits of confi guration parameter.
Bit number
Symbol
00
01
02
03
04
+
05
+
06
+
07
+
08
+
09
Not used
10
Not used
11
Not used
12
Not used
13
Not used
14
Not used
15
Not used
Tab. 1.b
Example:
It bit 00, 01, and 07 are set to “1“ the confi guration variable value = 131
(converted binary code to decimal code) and the sequence pressing
“mode“ buttos is:
Temperature sensor calibration
To adjust the temperature calibration, enter in the tC (Temperature
Calibration) menu, in un range compreso tra -5 e + 5 °C con incrementi
di ± 0,1 °C.
Humidity sensor calibration
Available only for the models with humidity sensor. To adjust the
humidity calibration, enter in the hC (Humidity Calibration) menu, in un
range compreso tra -10 a +10 UR % con incrementi di ± 0,1 UR%.
F
rost protection
If enabling the frost protection function (FE - Enable frost protection set
to: 0= Disabled; 1= Enabled), when the thermostat is turned off , and the
temperature is lower than “Ft”, the output will switch on the relay, and
the LCD display “
”; when the temperature is up to “Ft+2” °C, the output
will switch off the relay with the “
” disappear.
F
rost protection set point
The set the frost protection set point, enter in the Ft (Frost protection
temperature) menu and select the new value from 5,0 to 17,0 °C.
B
uzzer enable
To enable this operation, enter in the bE (Buzzer Enable) menu and
confi rm:
•
0= Disable;
•
1= Enable;
Key Lock
To enable this operation, enter in the LE (Lock Enable) menu and confi rm
the new value
•
0 = Disable;
•
1 = Enable;
Auto recovery
For internal use. It is fi x to 1;
Key
C
lock
To select the sequence of functions to show on display, enter in the
Parameters Menu and confi gure the parameter “tE” and with rotary
encoder select the new value turning right or left, then press “
”
to confi rm.
The following functions can be selected:
Value
Action
0
disabled
1
2
3
4
5
6
7
Tab. 1.c
The symbols can be turn on separately or in pairs and the sequence is
defi ned setting to “1” the diff erent bits of confi guration parameter.
Example:
If the confi guration variable value = 7, the sequence pressing “clock”
button is:
No time band ->
->
->