55
M
ask index
Displa
y Description
Description
Default
UOM
V
alues
Caf91
S1
Enable siz
e and siz
e f
or compr
essor g
roup 1 (line 1)
Si
10.0
---
kW
NO/SI
0.0…500.0
……
…
…
…
S4
Enable siz
e and siz
e f
or compr
essor g
roup 4 (line 1)
NO
---
---
kW
---
NO/SI
0.0…500.0
Caf92
S1
Enable stages and stages f
or compr
essor g
roup 1 (line 1)
Si
100
---
%
NO/SI
100; 50/100; 50/75/100;
25/50/75/100; 33/66/100
……
…
…
…
S4
Enable stages and stages f
or compr
essor g
roup 4 (line 1))
NO
---
---
kW
NO/SI
S1…S4
Caf93
C01
Siz
e g
roup f
or compr
essor 1 (line 1) or pr
esence of in
ve
rt
er
S1
---
S1…S4/INV
……
…
…
…
C12
Siz
e g
roup f
or compr
essor 6 (line 1)
S1
---
S1…S4
Caf95
M
in on time
M
inimum Dig
ital Scr
oll
TM
compr
essor On time (line 1)
60
s
0…999
M
in off
time
M
inimum Dig
ital Scr
oll
TM
compr
essor O
ff
time(line 1)
180
s
0…999
M
in time t
o
star
t same
compr
essor
M
inimum time bet
w
een star
ts f
or Dig
ital Scr
oll
TM
compr
essor (line 1)
360
s
0…999
Reac
tivat
e star
t-up
pr
ocedur
e af
te
r
Dig
ital Scr
oll
TM
compr
essor star
t-up pr
ocedur
e r
eac
tivation time (line 1)
480
min
0…9999
Cag01
M
inimum v
oltage
V
oltage cor
responding t
o
the minimum capacit
y of the in
ve
rt
er (line 1)
0
.0
V
0.0…10.0
M
aximum v
oltage
V
oltage cor
responding t
o
the maximum capacit
y of the in
ve
rt
er (line 1)
10.0
V
0.0…10.0
Nominal fr
eq
.
Nominal fr
equenc
y (nominal capacit
y at nominal fr
equenc
y) (line 1)
5
0
H
z
0…150
Nominal pow
e
r
Nominal capacit
y f
or compr
essor managed by in
ve
rt
er at nominal
fr
equenc
y (line 1)
10.0
Kw
0.0…500.0
Cag02
R
ising time
Time t
o
pass fr
om min capacit
y t
o
max capacit
y f
or modulating device
(line 1)
90
s
0…600
Falling time
Time t
o
pass fr
om max capacit
y t
o
min capacit
y f
or modulating device
(line 1)
30
s
0…600
Cag03
Enable compr
essor mo
-
dulation inside neutral
zone
Enable compr
essor 1 modulation inside Neutral z
one (line 1)
SI
---
NO /
YES
Cag04
Enable suc
tion pr
ess
.
back
up pr
obe
Enable scr
eens f
or suc
tion pr
essur
e back
up pr
obe confi
guration (line 1)
NO
---
NO /
YES
Cag05
Request in case of r
egu-
lat.pr
obe fault
C
ompr
essor f
o
rcing value in case of suc
tion pr
obes fault (line 1)
50.0
%
0.0…100.0
Cag06
Enable anti liquid r
etur
n
valv
e
Enable liquid non r
etur
n func
tion (line 1)
NO
---
NO /
YES
Cag07
Enable compr
essor en
ve
-
lop management (*)
Enable compr
essor en
velope management (scr
ew only).
For details on c
onfi
gur
ation c
ontac
t C
a
re
l.
NO
---
NO /
YES
T
he f
ollo
wing paramet
ers r
e
fer t
o
line 2, f
or details see the c
o
rr
esponding paramet
ers f
or line 1 abo
v
e