pRack +040000071 rel. 1.1 - 14.10.2011
15
ENG
I/O list
Digital outputs
NO1
Compressor 1
NO2
Compressor 1, unloader
NO3
Compressor 2
NO4
Compressor 2, unloader
NO5
Compressor 3
NO6
Compressor 3, unloader
NO7
Fan
NO8
Alarms output
Digital inputs
ID1
Suction HP pressostat
ID2
Suction LP pressostat
ID3
Compressor 1, thermal overload alarm
ID4
Compressor 1, oil alarm
ID5
Compressor 2, thermal overload alarm
ID6
Compressor 2, oil alarm
ID7
Compressor 3, thermal overload alarm
ID8
Compressor 3, oil alarm
ID9
Common fan overload
ID10
Inverter alarm
Analog outputs
Y1
Common condenser inverter
Analog inputs
B1
Suction pressure probe
4...20 mA
-0.5
..7.0 barg
B2
Condensing pressure probe
4...20 mA
0.0
..30.0 barg
B3
Suction temperature probe
NTC
B4
Discharge temperature probe
HTNTC
B5
External temperature probe
NTC
Tab. 2.f
Main parameters
Parameter
Mask index
Value
Suction regulation by
Cab01
PRESSURE
Suction regulation type
Cab03
NEUTRAL ZONE
Suction setpoint
Cab08
3.5,barg
Suction diff erential
Caf10
0.3 barg
Compressors rotation type
Caf04
FIFO
Refrigerant
Cae24
R404A
High suction pressure alarm threshold
Cae26
6.0 barg
Low suction pressure alarm threshold
Cab01
0.0 barg
Condenser regulation by
Dab01
PRESSURE
Condenser regulation type
Dab03
PROPORTIONAL BAND
Condenser setpoint
Dab07
12.0 barg
Condenser diff erential
Dae01
2.0 barg
High condenser pressure alarm threshold
Dae03
24.0 barg
Low condenser pressure alarm threshold
Cab01
7.0 barg
Tab. 2.g