Mechanical installation
WTS LARGE +0300131IT rel. 1.0 - 05.09.2022
5.2.6 Inserting the membrane(s)
Before installing the membranes in the membrane container, it must be ensured that the feed water line is closed and
thus no pressure is applied.
»
Dismantle the crescent-shaped metal plates.
»
Remove the cap of the membrane pressure vessels (by pulling it out upwards) with the enclosed disassembly
tool.
Disassembly tool
»
Remove the protective cover of the osmosis membrane (with sterile gloves) without damaging the
membrane. Do not remove the protective plastic film adhering to the osmosis membrane!
This can be recognised by the printed flow direction arrows.
»
Wet the seal of the osmosis membrane and the pegs at the ends with silicone fat if necessary.
»
Insert the membranes into the container as shown; pay attention to the position/direction of the seal.
Make sure that the lip seal is not damaged.
»
Reassemble the top caps of the containers in the correct position and secure them with the metal plates.
Check that the screw connection.
»
Re-attach the connectors to the lower part of the containers.
»
Make sure that there are no abnor- mal tensions on the lines or connections.
Notice:
Use disposable gloves when installing the pre-filter(s) and membrane(s) to protect them from
contamination.