Carel kVent Manual Download Page 28

 

kVent – rel 3.1 – 22/06/2018 

28

Mask 

code 

Description 

Type 

Default 

UoM 

Range 

R/W 

Variable Name 

BMS 

BacNet 

Y0ad 

Modulating supply fan - Hardware value 

Real 

 

 

ModulSupplyFan.HW_Val 

IR76 

AV76 

Y0ad 

Ziehl Abegg supply fan  - Actual speed [rpm] of the 
Zhiel-Abegg fan 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_1.CurrSpeed_rpm 

IR98 

PIV98 

Y0ad 

Ziehl Abegg supply fan  - Maximum set speed 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_1.MaxSpeed_rpm 

IR99 

PIV99 

Y0ad 

Ziehl Abegg supply fan  - Minimum set speed 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_1.MinSpeed_rpm 

IR100 

PIV100 

Y0ad 

Ziehl Abegg supply fan electrical informations - DC 
link voltage (V) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.DC_LinkV 

IR101 

PIV101 

Y0ad 

Ziehl Abegg supply fan electrical informations - 
Supply voltage (peak voltage) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.LineV 

IR102 

PIV102 

Y0ad 

Ziehl Abegg supply fan electrical informations - 
Fan level of speed controller (0-100%) 

USInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.Modulation 

IR103 

PIV103 

Y0ad 

Ziehl Abegg supply fan electrical informations - 
Motor input power (W) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.MotPwr 

IR104 

PIV104 

Y0ae 

Ziehl Abegg supply fan electrical informations - 
Electronics temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.ElectronicTemp 

IR105 

AV105 

Y0ae 

Ziehl Abegg supply fan electrical informations - 
IGBT temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.IGBT_temp 

IR106 

AV106 

Y0ae 

Ziehl Abegg supply fan electrical informations - 
MCU temperature 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.MCU_Temp 

IR107 

AV107 

Y0ae 

Ziehl Abegg supply fan electrical informations - 
Motr temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_1.MotTemp 

IR108 

AV108 

Y0af 

Return fan - Value 

Bool 

 

 

 

ExhFan.Ctrl 

DI6 

BV176 

Y0af 

Modulating return fan - Hardware value 

Real 

 

 

ModulExhFan.HW_Val 

IR79 

AV79 

Y0af 

Ziehl Abegg return fan speed informations - Actual 
speed [rpm] of the Zhiel-Abegg fan 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_2.CurrSpeed_rpm 

IR109 

PIV109 

Y0af 

Ziehl Abegg return fan speed informations - 
Maximum set speed 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_2.MaxSpeed_rpm 

IR110 

PIV110 

Y0af 

Ziehl Abegg return fan speed informations - 
Minimum set speed 

UInt 

 

 

 

MB_Devices.FanSpeedInfo_ZA

_2.MinSpeed_rpm 

IR111 

PIV111 

Y0af 

Ziehl Abegg return fan electrical info - DC link 
voltage (V) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.DC_LinkV 

IR112 

PIV112 

Y0af 

Ziehl Abegg return fan electrical info - Supply 
voltage (peak voltage) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.LineV 

IR113 

PIV113 

Y0af 

Ziehl Abegg return fan electrical info - Fan level of 
speed controller (0-100%) 

USInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.Modulation 

IR114 

PIV114 

Y0af 

Ziehl Abegg return fan electrical info - Motor input 
power (W) 

UInt 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.MotPwr 

IR115 

PIV115 

Y0ag 

Ziehl Abegg return fan electrical info - Electronics 
temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.ElectronicTemp 

IR116 

AV116 

Y0ag 

Ziehl Abegg return fan electrical info - IGBT 
temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.IGBT_temp 

IR117 

AV117 

Y0ag 

Ziehl Abegg return fan electrical info - MCU 
temperature 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.MCU_Temp 

IR118 

AV118 

Y0ag 

Ziehl Abegg return fan electrical info - Motr 
temperature (°C) 

Real 

 

 

 

MB_Devices.FanElectricalInfo_Z

A_2.MotTemp 

IR119 

AV119 

Y0ah 

Supply fan - Value 

Bool 

 

 

 

SupplyFan.Ctrl 

DI5 

BV172 

Y0ah 

Modulating supply fan - Hardware value 

Real 

 

 

ModulSupplyFan.HW_Val 

IR76 

AV76 

Y0ah 

EBM supply fan speed info - Current speed in 
[rpm] of the fan for Ebmpapst fan 

UInt 

 

rpm 

 

MB_Devices.InfoSpeed_EBM_1

.CurrSpeed 

IR120 

PIV120 

Y0ah 

EBM supply fan speed info - Maximum admissible 
speed: all read or speed in [rpm] settings are 
limited to this value for Ebmpapst fan 

UInt 

 

rpm 

 

MB_Devices.InfoSpeed_EBM_1

.MaxSpeed 

IR121 

PIV121 

Y0ah 

EBM supply fan electrical info - DC link voltage for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.ElectrInfo_EBM_1.

DC_Link_V 

IR122 

PIV122 

Y0ah 

EBM supply fan electrical info - DC link current for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.ElectrInfo_EBM_1.

DC_Link_A 

IR123 

PIV123 

Y0ah 

EBM supply fan electrical info - Current power in 
[W] for Ebmpapst fan 

UInt 

 

 

MB_Devices.ElectrInfo_EBM_1.

CurrPower 

IR124 

PIV124 

Y0ai 

EBM supply fan electrical info - Internal circuit 
temperature for Ebmpapst fan 

UInt 

 

°C 

 

MB_Devices.ElectrInfo_EBM_1.

ElectrTemp 

IR125 

PIV125 

Y0ai 

Current rotation direction 0: Left; 1: Right; for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.CurrRotDir_EBM_1 

IR126 

PIV126 

Y0ai 

EBM supply fan electrical info - Current modulation 
level  in [%] for Ebmpapst fan 

UInt 

 

 

MB_Devices.ElectrInfo_EBM_1.

CurrModulLev 

IR127 

PIV127 

Y0aj 

Return fan - Value 

Bool 

 

 

 

ExhFan.Ctrl 

DI6 

BV176 

Y0aj 

Modulating return fan - Hardware value 

Real 

 

 

ModulExhFan.HW_Val 

IR79 

AV79 

Y0aj 

EBM return fan speed info - Current speed in [rpm] 
of the fan for Ebmpapst fan 

UInt 

 

rpm 

 

MB_Devices.InfoSpeed_EBM_2

.CurrSpeed 

IR128 

PIV128 

Y0aj 

EBM return fan speed info - Maximum admissible 
speed: all read or speed in [rpm] settings are 
limited to this value for Ebmpapst fan 

UInt 

 

rpm 

 

MB_Devices.InfoSpeed_EBM_2

.MaxSpeed 

IR129 

PIV129 

Y0aj 

EBM return fan electrical info - DC link voltage for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.ElectrInfo_EBM_2.

DC_Link_V 

IR130 

PIV130 

Y0aj 

EBM return fan electrical info - DC link current for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.ElectrInfo_EBM_2.

DC_Link_A 

IR131 

PIV131 

Y0aj 

EBM return fan electrical info - Current power in 
[W] for Ebmpapst fan 

UInt 

 

 

MB_Devices.ElectrInfo_EBM_2.

CurrPower 

IR132 

PIV132 

Y0ak 

EBM return fan electrical info - Internal circuit 
temperature for Ebmpapst fan 

UInt 

 

°C 

 

MB_Devices.ElectrInfo_EBM_2.

ElectrTemp 

IR133 

PIV133 

Y0ak 

Current rotation direction 0: Left; 1: Right; for 
Ebmpapst fan 

UInt 

 

 

 

MB_Devices.CurrRotDir_EBM_2 

IR134 

PIV134 

Y0ak 

EBM return fan electrical info - Current modulation 
level  in [%] for Ebmpapst fan 

UInt 

 

 

MB_Devices.ElectrInfo_EBM_2.

CurrModulLev 

IR135 

PIV135 

Y0ax 

Current version of the application according to 
standard - X version of the application 

UInt 

 

 

 

CurrVer.X 

IR178 

PIV178 

Y0ax 

Current version of the application according to 
standard - Y version of the application 

UInt 

 

 

 

CurrVer.Y 

IR179 

PIV179 

Y0ax 

Current version of the application according to 
standard - Z version of the application 

UInt 

 

 

 

CurrVer.Z 

IR180 

PIV180 

Y0ax 

Current version of the application according to 
standard - Beta version enable 

Bool 

 

 

 

CurrVer.IsBeta 

DI223 

BV494 

Y0ax 

Current version of the application according to 
standard - D version of the application 

UInt 

 

 

 

CurrVer.D 

IR181 

PIV181 

Y0ax 

Application version 

UDInt 

 

 

 

GeneralMng.OsVersion[1] 

IR182 

PIV182 

Summary of Contents for kVent

Page 1: ...kVent rel 3 1 22 06 2018 1 kVent Controller for ventilation units Manual H i g h E f f i c i e n c y S o l u t i o n s...

Page 2: ...kVent rel 3 1 22 06 2018 2...

Page 3: ...ontrollers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and...

Page 4: ...kVent rel 3 1 22 06 2018 4...

Page 5: ...CO2 Regulation 25 5 12 Boost function 25 5 13 Minor functions 25 5 14 Import Export parameters 25 6 PARAMETERS TABLE 26 6 1 INFO menu in main mask 26 6 2 SET menu in main mask 29 6 3 MODE menu in mai...

Page 6: ...e control Air flow control Protection Filters Fire Smoke alarm Frost protection Door switch Interface Browser interface based on WebKit pGDE for advanced function and service thTune for end user 3 dif...

Page 7: ...cables be laid parallel to the power cables Keep the paths of the probe cables as short as possible and avoid making spiral paths that enclose power devices In case of malfunctions do not attempt to r...

Page 8: ...ame FieldBus port for ModbusMaster 19200 8N2 With the following parameters is possible to define a different Frame Ha91 Stop bits Ha92 Parity Display protocol on port DISP ModBus master protocol on po...

Page 9: ...alog outputs Out Y PWM output not optically isolated 2 Analog outputs Out Y Output for single pole stepper motor 1 TOTAL ANALOG OUTPUTS 2 Digital outputs Out NO NC relay output 1 Out NO relay output 5...

Page 10: ...kVent rel 3 1 22 06 2018 10 Connections example 2 4 3...

Page 11: ...ure AI4 Fresh temperature AI3 Recovery ON OFF DO10 Recovery 3point valve DO23 DO24 Modulating recovery AO6 Recovery 2 steps DO36 DO37 3 Glycol Supply temperature AI1 Exhaust temperature AI4 Fresh temp...

Page 12: ...ve control Back water temperature AI6 Fresh temperature AI3 Heat 1 DO4 Modulating heat AO3 Heat 2 DO6 Heat 3 point valve DO17 DO18 Cool Heat common AO12 3 0 10V valve in common with cool Back water te...

Page 13: ...3 point valve DO27 DO28 Modulating preheater AO7 4 1 modulating After preheater temperature AI11 Modulating preheater AO7 Preheater back water temperature AI10 Preheater 3 point valve DO27 DO28 Prehea...

Page 14: ...ulating exhaust fan AO2 1 VAV Supply air pressure AI13 Exhaust air pressure AI14 Modulating supply fan AO1 Modulating exhaust fan AO2 2 CAV Supply air pressure AI13 Exhaust air pressure AI14 Modulatin...

Page 15: ...r 14 Ga66 Exhaust air pressure 12 Gb23 Comfort 11 Gc21 Preheater 11 Gd11 IEC 15 Ga 71 Supply humidity 13 Gb25 Supply filter alarm 12 Gc23 Humidifier 12 Gd12 Cool Heat signal 24 GaB6 VOC sensor 14 Gb27...

Page 16: ...update the application software of the controllers family with the following methods 1 Update from computer by USB cable 2 Update via USB flash drive 3 Update with file transfer via FTP Attention only...

Page 17: ...directory on the computer to the UPGRADE directory on the kVent controller 3 Access the system menu on the kVent and select UPGRADE Note when having loaded the update file to the UPGRADE directory vi...

Page 18: ...and probes are available in a menu connected to the synoptics The individual screens of the synoptics are shown below Set In this menu is possible to see the current setpoint and the working mode def...

Page 19: ...ck Enable scheduler Clock 2s thTune scheduler settings Fan Change working setpoint 1 ECO 2 PRECOMFORT 3 COMFORT 4 STOP On Off Switch ON OFF th Tune display Exit from settings Clock Mode for 3s Run boo...

Page 20: ...e comfort zones are ECO PRECOMFORT and COMFORT This working mode can change the following sets if the functions are activated 1 Supply temperature a Economy Z001 b Precomfort Z002 c Comfort Z003 2 Roo...

Page 21: ...ured by Service I003 No serious alarm On by digital input On by the OR of the following conditions o On by pGD X00a o On by BMS o On by thTune if present o On by scheduler if enabled Variable mode is...

Page 22: ...reshold The bypass damper can be modulated to reach the desired temperature for the supply air temperature because the freecooling can be considered as the first step of sequential PID regulation In c...

Page 23: ...e below an example with devices with the same power Min inverter power 20 Max heaters power 33 3kW In this case the second heater will start when the request reach the threshold calculated in the foll...

Page 24: ...decrease the efficiency of the unit kVent provides a control on external temperature and after preheater device If the unit has a preheater the after preheater temperature is considered for recovery...

Page 25: ...mode menu X00b or by TH Tune pressing thogheter the buttons Clock Mode for 3s The maximum Boost time is settable on the Setting menu through the parameter H023 5 13 Minor functions Antistack procedure...

Page 26: ...0l Supply humidity probe Probe value Real rh R SupplyHum ReadVal IR88 AV88 Y00l Suction temperature probe Probe value Real rh R FreshAirHum ReadVal IR89 AV89 Y00l Return CO2 sensor Probe value Real pp...

Page 27: ...nt valve close Value Bool R CoolVlv_Cl Ctrl DI84 BV269 Y00y Reverse 3point valve open Hardware value Bool R CoolHeatVlv_Op HW_Val DI85 BV270 Y00y Reverse 3point valve open Value Bool R CoolHeatVlv_Op...

Page 28: ...8 Y0ag Ziehl Abegg return fan electrical info Motr temperature C Real R MB_Devices FanElectricalInfo_Z A_2 MotTemp IR119 AV119 Y0ah Supply fan Value Bool R SupplyFan Ctrl DI5 BV172 Y0ah Modulating sup...

Page 29: ...dity setpoint Economy Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP Economy HR7 AV7 Z008 Humidity setpoint PreComfort Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP PreComfort HR8 AV8 Z009 Humidity setpoin...

Page 30: ...ed 0 StartMont h HR48 PIV48 Z00e Last day of period USInt 2 1 31 R W Scheduler_OnOffUnit Scheduler _1 VacationsSched 0 EndDay HR49 PIV49 Z00e Last month of period USInt 1 1 12 R W Scheduler_OnOffUnit...

Page 31: ...PIV77 Z00f Special month USInt 1 1 12 R W Scheduler_OnOffUnit Scheduler _1 SpecDaysSched 5 SpecialM onth HR78 PIV78 Z00f Unit status of the special day 0 OFF 1 ECONOMY 2 PRE COMFORT 3 COMFORT 4 AUTO...

Page 32: ...R210 PIV210 A042 Time minimum ON ON reheater device UInt 60 s 0 65535 R W ReHeatMinOnOnSameT HR211 PIV211 A043 Minimum reheater hot water valve Real 20 0 0 0 100 0 R W ReHW_MinPID HR212 AV212 A044 Min...

Page 33: ...Hours counter reverse 2nd step UDInt 0 0 999999 R W HC_Rev_2 MaintThrsh HR326 PIV326 C006 Hours counter reverse 2nd step Bool 0 1 R W HC_Rev_2 Res C38 BV814 C007 Reverse device 2nd step Manual value U...

Page 34: ...999 9 R W ManSupplyFanIdle HR151 AV151 D025 Delay to switch OFF supply fan UInt 70 s 0 65535 R W DOff_SupplyFan HR152 PIV152 D026 Delay between fan and damper UInt 15 s 0 65535 R W DT_Dmp HR153 PIV15...

Page 35: ...ating running Bool 0 1 R W FastHeatTrig C30 BV734 E032 Fast heating stop Bool 0 1 R W FastHeatStop C31 BV735 E033 Fast heating time UInt 1500 s 0 65535 R W FastHeatT HR272 PIV272 E034 Fast cooling thr...

Page 36: ...999 9 999 9 R W AI_ReadFnt 4 Param Min_Val HR781 AV781 Ga19 Analog input functions Maximum value Real 105 0 C 999 9 999 9 R W AI_ReadFnt 4 Param Max_Val HR782 AV782 Ga20 Analog input functions Offset...

Page 37: ...nt 0 0 70 R W AI_ReadFnt 15 Ch HR844 IV844 Ga72 Analog input functions Type USInt 43 0 50 R W AI_ReadFnt 15 Param Typ HR846 PIV846 Ga73 Analog input functions Minimum value Real 0 0 rh 999 9 999 9 R W...

Page 38: ...5 Analog input functions Offset Real 0 0 rh 99 9 99 9 R W AI_ReadFnt 25 Param Offset HR909 AV909 DIGITAL IN SET menu 6 10 2 Mask code Description Type Default UoM Range R W Variable Name BMS BacNet Di...

Page 39: ...s Priority USInt R DI_ReadFnt 20 Prio IR405 PIV405 Digital input functions Status Bool R DI_ReadFnt 20 Hw_Val DI270 BV1797 Gb39 Digital input functions Channel DInt 0 0 70 R W DI_ReadFnt 20 Ch HR948 I...

Page 40: ...ctions Channel DInt 0 0 50 R W DO_ReadFnt 15 Ch HR984 IV984 Gc30 Digital output functions Logic Bool FALSE 0 1 R W DO_ReadFnt 15 Logic C311 BV1870 Digital output functions Priority USInt R DO_ReadFnt...

Page 41: ...igital output functions Status Bool R DO_ReadFnt 35 Hw_Val DI308 BV1948 Gc69 Digital output functions Channel DInt 0 0 70 R W DO_ReadFnt 35 Ch HR1024 IV1024 Gc70 Digital output functions Logic Bool FA...

Page 42: ...72 PIV472 Analog output functions Request Real R AO_ReadFnt 10 Hw_Val IR473 AV473 Gd10 Analog output functions Channel DInt 0 0 60 R W AO_ReadFnt 10 Ch HR1066 IV1066 Analog output functions Priority U...

Page 43: ...s_PreHeat Economy_Ti HR1113 IV1520 H033 Modes set PID regulations PreHeat Real 5 0 999 9 999 9 R W PIDs_PreHeat Precomfort_Kp HR1132 AV1539 H034 Modes set PID regulations PreHeat Int 120 s 0 65535 R W...

Page 44: ...uration not allowed Alarm status Bool R Al_UnitCfgError Active DI1037 BV2068 I001 Recovery application code USInt 0 0 4 R W AppCode_Rec HR83 PIV83 I001 Application heating code USInt 0 0 4 R W AppCode...

Page 45: ...wing alarms log display screen The alarms log memorizes the kVent operation status when the alarms are triggered Each log entry is an even that can be displayed from among all of the events available...

Page 46: ...eset Stop humidifier Al_SupplyAirHum_Prb DI1036 BV1036 A037 Unit configuration not allowed Auto reset Stop unit Al_UnitCfgError DI1037 BV1037 A038 Supply fan Offline Auto reset Stop unit Al_Offline_ZA...

Page 47: ...current Auto reset Stop unit Al_LimMainsA_EBM_2 DI1107 BV1107 A108 Return fan Brake mode Auto reset Stop unit Al_BrakeMode_EBM_2 DI1108 BV1108 A109 Return fan Cable break Auto reset Stop unit Al_Cable...

Page 48: ...m the release 2 1 0 there is the possibility to setup a different PID values for each devices in base of the working mode set The enabling is manage under the menu Settings parameter H028 8 4 HEPA fil...

Page 49: ...ed the unit of measure from s to min on the time setting for the pump on the heating coils during the off time Fixed the DEV configuration changed FloatValve management now at the startup of the unit...

Page 50: ...ant value added all the masks to set up the PID parameters for each coils in base of the working mode added the fresh modulating damper Condensing Unit Management Add the RU language Add the CZ langua...

Page 51: ...kVent rel 3 1 22 06 2018 51...

Page 52: ...changes or modifications to its products without prior notice All trademarks hereby referenced are the property of their respective owners CAREL is a registered trademark of CAREL INDUSTRIES Hqs in It...

Page 53: ...kVent rel 3 1 22 06 2018 53 CAREL INDUSTRIES S p a Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com...

Reviews: