5. FUNCTIONS
5.1 Input functions
Here below the list of analog inputs functions:
AI
Code
Analog input
Function
1
Ga01
Supply temperature
Main temperature regulation
2
Ga06
Return temperature
Supply setpoint compensation
Fire alarm activation
3
Ga11
External temperature
Recovery control and defrost
FreeCooling/freeheating
Cool/Heat mode changeover
Antifreeze and antifrost control
Fast heating function
4
Ga16
Exhaust temperature
Fire alarm in case of return probe
broken
6
Ga26
Back water temperature
Antifreeze control
10
Ga 46
Preheater back water
temperature
Antifreeze control
11
Ga51
After preheater
temperature
Main preheating regulation
Recovery defrost
12
Ga56
CO2 sensor
Fresh air regulation
13
Ga61
Supply air pressure
VAV and CAV regulation
14
Ga66
Exhaust air pressure
VAV and CAV regulation
15
Ga 71
Supply humidity
Main humidity regulation
24
GaB6
VOC sensor
Fresh air regulation
25
GaC1
Fresh air humidity
Freecoling/freeheating enabling
Here below the list of digital inputs functions:
DI
Code
Digital input
Function
1
Gb01
Fire alarm
Fire alarm activation
2
Gb03
Fan overload
Stop unit
3
Gb05
Humidifier alarm
Stop humidifier
4
Gb07
Remote On
Start/Stop the unit with timings
5
Gb09
Summer/Winter
Define working mode
6
Gb11
Cooling alarm
Stop cooling
8
Gb15
Freeze alarm
Stop ventilation
Force heating valve at 100%
9
Gb17
Heating alarm
Stop unit and force ventilation ON
10
Gb19
Eco
Force unit in Economy mode
11
Gb21
Precomfort
Force unit in Precomfort mode
12
Gb23
Comfort
Force unit in Comfort mode
13
Gb25
Supply filter alarm
Warning dirty filter
14
Gb27
Supply filter alarm 2
Warning dirty filter
15
Gb29
Return filter alarm
Warning dirty filter
21
Gb41
Supply air flow switch
Check air flow and stop unit
22
Gb43
Return air flow switch
Check air flow and stop unit
23
Gb45
Recovery clogged
Recovery in defrost mode
24
Gb47
Door Switch
Door open
5.2 On request
The On status requires the AND logic of:
•
Unit configured by Service (I003)
•
No serious alarm
•
On by digital input
•
On by the OR of the following conditions:
o
On by pGD (X00a)
o
On by BMS
o
On by thTune, if present
o
On by scheduler, if enabled
Variable mode is shared with all the control sources.
If any condition go to OFF, the unit will turn OFF.
5.3 Cooling/Heating changeover
The external and room/return temperatures are considered: if
the external temperature is lower than a minimum threshold or
greater than a upper threshold the heating or cooling mode
can be forced:
In the middle, between the heating and cooling external
temperature thresholds, or when the external temperature
probe isn’t available the heating or cooling mode will be
decided considering the room temperature or the return
temperature (if the probes are available), here below it is
represented the behaviour in case of room temperature:
If the room temperature is greater than the setpoint, the unit
starts in cooling mode and remains in cooling mode until the
room temperature becomes lower than the setpoint for a
settable delay (H013), then the heating mode is activated. In
the same way, if the starting temperature is lower than the
setpoint the unit starts in heating mode and remains in heating
mode until the room temperature becomes greater than the
setpoint for the same delay.
5.4 Temperature regulation strategy
Compensation
5.4.1
The regulation of the unit could be done according the return,
supply or room set.
In case of return or room regulation, kVent provides the
compensation control strategy, based on return or room and
external temperature. Compensation modulate the supply
setpoint between the minimum and maximum supply setpoint.
Final supply setpoint is calculated as following:
%
%
%
-100% is equal to maximum supply setpoint and 100% is equal
to minimum supply setpoint, as in the following graph:
External temp.
Cooling
Heating
Based on room temp.
H011
H012
Supply temp.
Cooling
Heating
Delay
Delay
Supply setpoint
2.0°C
2.0°C
0
Max cool
H010
External temperature compensation
100
-100
Min cool
H009
Min heat
H007
Max heat
H008
Return temperature compensation
Return set
100
0
-100
PID regulation
H005
H006
Min set
H002
Max set
H001
-100%
100%
Supply
set