"humiFog direct" +0300073EN rel. 1.2 - 02.05.2019
5.3 Touch display
HOME menu
The “HOME” menu includes information about the pumping station and
the zones, including current production, information on the probes and
unit status.
11
1
2
4
5
3
6
7
8
9
10
Fig. 5.d
Pos. Function
Pos. Function
1
ON/OFF quick menu
7
Notification centre
2
Set point quick menu
8
System date & time
3
Input/output quick menu
9
Scheduler status
4
System information quick menu
10
Master/Slave Network
5
Descriptive icon of zone status
11
Main menu
6
Alarm list
Tab. 5.b
5.3.1
ON/OFF quick menu
Pressing the ON/OFF quick menu icon accesses the screen for switching
the entire system or individual zones on and off. To switch on or off the
unit or zones (ON when the indicator is positioned to the right, OFF when
positioned to the left), press the button.
Message
Values Meaning
Unit
ON
Enables the pump to operate according to zone request
OFF
Switches the pumping unit OFF
Zone 1/2
(visible only
if unit ON)
START Enables atomisation in zone 1/2 according to the request
PAUSE Temporarily stop atomisation in zone 1/2
Tab. 5.a
The menu also contains information on the type of system start-up
control signal. To return to the home menu, press the “HOME” icon
Fig. 5.e
5.3.2
Set point quick menu
Press the icon to access the menu. The menu is used to modify the set
point and proportional control band. Press the white number to change
the value. Enter the desired value and press the confirm button (
).
Title
Message
Values
Default
Zone 1 set
(Zone 2 set)
Main probe set point
0-100% rH 0-40 °C
50% rH 25 °C
Main probe band
0-10% rH 0-10 °C
5% rH 2 °C
Limit probe set point
0-100% rH 0-40 °C
80% rH 15 °C
Limit probe band
0-10% rH 0-10 °C
5% rH 2 °C
Tab. 5.c
To move from one area to another, or from one page to another, press
the right and left arrows on the display and repeat the same operations
to change the values.
To return to the home menu, press the “HOME” icon
Fig. 5.f
5.3.3
INPUT/OUTPUT quick menu
Press the icon to access the menu.
The input/output dashboard offers an intuitive and real-time view of the
system operating status, the values read by the humiFog direct cabinet
probes, the status of the mechanical components in the water circuit and
the water flow path.
Mechanical component I/O dashboard
symbol
System components
Solenoid valve
(Valve closed)
(Valve open)
FV: cabinet fill valve
BYP: bypass valve
DC: cabinet drain valve
FV1: zone 1 fill valve
DR1: zone 1 drain valve
FV2: zone 2 fill valve
DR2: zone 2 drain valve
Pressure sensor
LPS: low pressure sensor
RHP: high pressure sensor
Temperature sensor
T: water temperature sensor
Pressure switch
HP: high pressure switch
Pump
Cabinet pump
Nozzles
(Atomise ON
(Atomise OFF)
Zone nozzles
Tab. 5.d
To return to the home menu, press the “HOME” icon
Fig. 5.g
To switch to display the input/output values in table form, press the right
arrow.
If using wireless probes, to display the input/output values, press the
right arrow again.
Use the slider to scroll through the table.
To return to the previous display, press
To return to the home menu, press the “HOME” icon
Fig. 5.h