Carel HB200C0300CE0 User Manual Download Page 24

24

ENG

Heos BOX R704

 +0300140EN - rel. 1.0 - 25.05.2022

4.9.2  Conformity to EMC directive

Heos Box is designed in compliance with the harmonised standards 
of the EMC directive 2014/30/EU. Heos Box is a partly-completed 
machine and as such must be appropriately incorporated into an 
evaporator system; compliance with the EMC directive must therefore 
be verified in the application, after final assembly. Contact Carel for 
suggestions and guidelines.

Notice:

 

the length of the earth wire for the electronic controller 

main power supply and digital output connections should be minimised, 
using the earthing points provided inside the electrical panel (positions 41 
and 42 in Figure 2.j) .

4.6  Kit installation

4.6.3  Anti-sweat heater kit

•  Before opening the electrical panel, move disconnect switch QS1 to 

OFF;

•  Installation involves the DIN rail on the vertical panel in the electrical 

panel (no. 65) and the electronic controller, and will require the use of a 
flat-head screwdriver to press the spring terminals.

•  Install the fuse carrier (marked FU4) and the SSR relay (marked KR1) and 

the two pre-wired terminals on the DIN rail (no. 65), as shown in the 
wiring diagram on page +QE&ETL/6;

•  Wire the cables marked 01 and 04 to terminals 1 and 2 (as per the wiring 

diagram);

•  Wire the cables marked 201 and 200 to electronic controller terminal J10 

(as shown in the wiring diagram);

•  Complete the wiring by connecting the anti-sweat heater power cables 

to terminals 3 and 4

•  Close the electrical compartment and move the disconnect switch to 

ON to restart the unit.

4.6.4  WiFi gateway kit

•  Before opening the electrical panel, move disconnect switch QS1 to 

OFF;

•  The parts of the box to be worked on are the electronic controller and 

the external interface (where all the electrical panel I/Os are located);

•  Now connect the wires downstream of the kit, marked 08 and 09, 

to terminal J25, as shown on page +QE&EFS/7 of the panel’s wiring 
diagram, using a flat-head screwdriver to help lever the spring;

•  When connecting the wires, make sure that the tip of the wire is fully 

inserted in the opening provided on the terminal;

•  Then install the WiFi gateway marked A2 on the holes provided on the 

external panel interface (where all the electrical panel I/Os are located), 
using the two screws provided together with the kit, in the space 
designated as “WIFI optional” in Figure 2.j, position 61;

•  Now run the two cables connected to gateway A2 through the cable 

gland marked “Supervision” in Figure 2.j, position 51, then firmly tighten 
the cable gland. All of the work to be done outside of the panel is now 
complete;

•  Proceed by wiring these two cables inside the panel. Connect the 3 

wires marked 37-38-15 to terminal J14 on the controller, and the wires 
marked 08 and 09 to terminal J25, as shown on page +QE&EFS/7 of the 
panel’s wiring diagram, using a flat-head screwdriver to help lever the 
spring;

•  Close the electrical compartment and move the disconnect switch to 

ON to restart the unit.

4.7  Refrigerant charging procedure

The HEOS BOX unit is designed to work only with R744 (CO2): only use 
R744 certified refrigerant to charge the HEOS BOX unit. 

The following points should be considered general indications for correctly 
charging refrigerant into the unit, and are not technical specifications. 

The expansion valves on the units must be correctly sized in order to 
complete the charging operation successfully. 

CAREL Industries S.p.A. may in this case, based on specific agreements, act 
as a consultant for the design/installation/commissioning/use of the unit, 
however in no case does it accept liability for incorrect operation of the 
unit and the overall system if the warnings or suggestions provided in this 
manual or in other product technical documents are not heeded. 
In order to charge the unit (as described in the steps listed below), use 
an interface (smartphone app or PC software) so as to monitor some 
operating variables that are useful in the refrigerant charge process (such 
as superheat). 

For details on using the Carel Heos Box unit, see the manual 
(+0300145EN).

The recommended sequence is as follows:
1.  Electrically disconnect HEOS BOX using the on/off switch on the unit 

and the disconnect device upstream of the unit’s power supply line. 
Then remove the refrigerant circuit cover panel.

2.  Check that the refrigerant inlet and outlet shut-off valves (18 and 21 

in Fig. 2.i) are open

3.  Using a vacuum pump, bring the system to a pressure of less than 0.25 

mbars (187 μmHg), medium vacuum. The time the circuit is kept in a 
vacuum must be evaluated on site, according to the volume of the 
circuit and in any case must not be less than 60 minutes.

4.  Prepare a system to weight the amount of refrigerant charged into the 

unit, and write the value on the rating label affixed in this document 
and to the HEOS BOX structure.

5.  Charge the unit with a refrigerant pre-charge (e.g. 2 kg - 4.4 lbs) in 

order to activate the control system and switch on the compressor.

6.  Check that the electronic valve stators are installed correctly
7.  Power on HEOS BOX using the on/off switch on the unit and the 

disconnect device upstream of the unit’s power supply line.

8.  Set the Heosbox unit to OFF

 

9.  Set parameter CSM (max custom speed) to a value of 80 rps 
10.  Set the water-glycol inlet temperature to 15°C (with nominal flow-rate)
11.  Set the HEOS BOX unit to ON and make sure that the compressor is 

close to the maximum speed allowed (80 rps), while making sure that 
the unit operates within the range stated in paragraph 2.6.2.

12.  Make sure that the compressor remains running at the maximum 

allowed speed (80 rps) for a few minutes (air control temperature close 
to the set point; for a multi evaporator configuration, the air control 
temperature must be close to the set point on each unit)

13.  If the superheat is greater than the set point (SH > SHset) and the 

expansion valve/valves are fully open (EEV%=100%), add refrigerant 
(e.g. 100/200 g) (for a multi evaporator configuration, the superheat 
on each evaporator must be monitored as described here).  To check 
the superheat set point, see the Carel Heos manual, as described 
previously.

14.  Wait a few minutes to let the system stabilise.
15.  Repeat the previous two steps until SH=SHset and EEV%<70% (for 

multi evaporator configurations this must be checked for each valve).

16.  Check the refrigerant temperature in the section of piping leaving 

the condenser and make sure that subcooling is between 0 and 4K 
(optimum value 3K) (0<SBC<4K) 

17.  After having correctly charged the refrigerant, carefully check for leaks 

using suitable instruments.

18.  Reset parameter CSM (max custom speed) to the default value of 100 rps

Summary of Contents for HB200C0300CE0

Page 1: ...C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT HEOS BOX R744 User manual Assembly instructions including user and maintenance inf...

Page 2: ......

Page 3: ...uit 12 2 11 Electrical panel 13 2 12 Requirements for positioning the unit and multi evaporator layout 14 3 HANDLING 19 3 1 Opening the packaging 19 3 2 Positioning the unit 19 4 INSTALLATION 21 4 1 M...

Page 4: ......

Page 5: ...EQUIPMENT HAZARD The unit is supplied sealed with an inert gas nitrogen pre charge of around 1 bar 14 5 psi above atmospheric pressure Take all necessary precautions to avoid material from being expe...

Page 6: ...equivalent new equipment on a one to one basis or one to zero for equipment less than 25 cm on their longest side 3 the equipment may contain hazardous substances the improper use or incorrect dispos...

Page 7: ...d with a Carel unipolar electronic expansion valve which is not supplied with the unit Appropriate sizing of the electronic valve where possible using Carel s selection tools allows Heosbox to be used...

Page 8: ...configuration HBOPZGATY2000 Kit for supervisor WiFi connection HBOPZRAHY2000 Anti sweat heater management kit Tab 2 d 2 5 Connection diagrams local and su pervisor connection The Heosbox unit can be c...

Page 9: ...y and therefore an external switch is needed for connection to the supervisory system Ethernet network Modbus Ethernet switch Fig 2 e On request a version of the controller with two Ethernet ports is...

Page 10: ...edium temperature operation Evaporating temperature 10 C superheat 10 K subcooling 0 K condensing temperature 20 C compressor rotation speed 80 rps 4 Nominal conditions for low temperature operation E...

Page 11: ...ulation of the current supplied by the electronic control does not include the optional anti sweat heater kit In fact the optional kit is not powered by the electronic controller but by the Heos Box m...

Page 12: ...nser Water outlet connection Water inlet connection Suction pressure line Discharge Line Fig 2 h 2 26 30 29 1 14 15 8 12 13 25 22 6 17 16 23 24 4 9 10 11 27 19 18 7 20 28 21 5 3 Fig 2 i Ref Descriptio...

Page 13: ...earth wire connection 43 Anti sweat heater kit 44 Electrical panel main switch 45 Electric panel ventilation air intake grille 46 Electrical panel power cable gland 47 Cable gland for digital output 6...

Page 14: ...other acceptable configuration involves a common liquid line NB the last evaporator also needs to be well supplied with liquid and the suction lines in a multisplit arrangement Multiplex configuration...

Page 15: ...ox Fig 2 p Heos Box lower than the evaporator P trap Reverse trap Suction line Heosbox Fig 2 q Possible oil top up Caution refer to section 4 6 2 12 3 Evaporator combination requirements When sizing t...

Page 16: ...6 0 755 1 319 2 304 3 634 5 154 7 002 11 464 25 0 271 0 692 1 209 2 113 3 333 4 727 6 422 10 514 Tab 2 p MT application medium temperature Minimum cooling capacity in kW to ensure the oil is carried t...

Page 17: ...ling capacity needed to carry the oil The tables below show the minimum cooling capacity as a function of Operating conditions Pipe diameter For the optimum diameter make sure that the required design...

Page 18: ...420 5 395 7 652 10 396 17 020 20 0 409 1 043 1 821 3 181 5 019 7 117 9 670 15 831 25 0 375 0 956 1 670 2 917 4 602 6 526 8 867 14 516 Tab 2 w Minimum cooling capacity in kW to ensure the oil is carrie...

Page 19: ...installed on the floor observing the clearances and making sure that there is natural ventilation to the unit Always avoid positioning installing the unit outdoors in a place where it is exposed to t...

Page 20: ...ed for correct operation of the unit the following images show the distances from the surfaces to be allowed for during installation Side view Top view wall wall MIN 150 mm 5 91 in MIN 150 mm 5 91 in...

Page 21: ...e using pipe couplings whose diameter and thickness varies according to the size of the unit see Refrigerant connections 4 1 Material supplied Heos Box is supplied complete with the following material...

Page 22: ...ff placing disconnect switch QS1 and the switch or disconnect device on the HEOS BOX power supply line in the OFF position see the wiring diagram The mains power disconnect device must have a contact...

Page 23: ...o the HEOS BOX power supply line in accordance with national regulations It is compulsory to follow the instructions on the wiring diagrams and comply with the minimum sizes of the multi core cables s...

Page 24: ...gerant into the unit and are not technical specifications The expansion valves on the units must be correctly sized in order to complete the charging operation successfully CAREL Industries S p A may...

Page 25: ...n 30 minutes 10 Disconnect the pump and close the discharge pressure port Fig 2 i 3 11 Carefully open the refrigerant inlet and outlet shut off valves Fig 2 i 18 and 21 4 8 2 Multi evaporator ME Cauti...

Page 26: ...the Electrical Connections have been carried out as described in paragraph 4 4 4 Make sure that there is at least one display kit available see paragraph 2 3 If wanting to use the interface via smart...

Page 27: ...outside of the unit Maintenance operations to be carried out every six months visually inspect the inside of the box every six months It is forbidden to remove the outer protection panels without firs...

Page 28: ...l output 5 5 Free cable gland 1 17 Cable gland for digital output 6 6 Free cable gland 2 18 Heos electronic controller fuses 7 Free cable gland 3 19 Auxiliary terminals for optional anti sweat heater...

Page 29: ...Now connect the wires downstream of the kit marked 08 and 09 to terminal J25 as shown on page QE EFS 7 of the panel s wiring diagram using a flat head screwdriver to help lever the spring When connect...

Page 30: ...30 ENG Heos BOX R704 0300140EN rel 1 0 25 05 2022 Notes...

Page 31: ......

Page 32: ...BEL Caution Do not remove this copy of the unit label from the manual The customer is required to carefully keep all of the documentation supplied with the unit for any future maintenance or service U...

Reviews: