4. INSTALLATION
The unit is installed and commissioned as described below;
please see the Carel “Heos” manual (+0300145EN) for details
on programming it.
Notice:
the water and refrigerant connections are located on the
opposite side to the electrical connections (Fig.4.a):
10
30
11
20 19
Fig. 4.a
Ref.
Description
11
Water inlet connection: 1” GAS threaded male
10
Water outlet connection: 1” GAS threaded male ( CE vers.)
20
Refrigerant inlet connection (*)
19
Refrigerant outlet connection (*)
30
Safety valve outlet connection 3/8” GAS threaded male
• fit appropriately-sized expansion vessels to avoid water hammer from
damaging the system;
• install mechanical and/or magnetic filters to minimise the presence of
impurities in the circuit.
Caution:
The water connections must always be completed by
qualified personnel who have the qualifications and authorisations
required by local regulations, using appropriate personal protective
equipment (PPE), who are aware of the necessary precautions and who are
able to correctly and safely complete all required operations.
Caution:
The PS and TS values for the water circuit connected to the
HEOS BOX refer to the lowest PS or TS of all the components in the circuit.
The unit’s water connections have 1” GAS male threads on the CE versions;
the unit should be connected to the water loop without any reductions
in diameter, as such reductions may affect the unit’s performance or
(*):
the water and refrigerant connections are located on the opposite
side to the electrical connections, as shown in the figure: the refrigerant
connections are made using pipe couplings whose diameter and thickness
varies according to the size of the unit, see “Refrigerant connections”.
4.1 Material supplied
Heos Box is supplied complete with the following material:
• Assembly and maintenance instructions;
• Wiring diagram;
• Safety valve calibration certificate;
• Carel PSD2 compressor driver technical leaflet;
• 3 temperature probes NTC060HP00;
• 1 temperature probe NTC060HF01;
• spare fuse kit (described in Tab. 4.a)
Protection description
Quantity
supplied
Fuse
model
HB200C0300CE0
HB200C0400CE0
HB200C0600CE0
HB200C1000CE0
Inverter power supply
2
10.3 x 38
20 A gG
20 A gG
32 A gL
25 A gG
Electronic controller power supply
2
10.3 x 38
32 A gL
32 A gL
32 A gL
32 A gL
Digital output 1, 2, 3, 4, 5
5
5 x 20
10 A time lag
10 A time lag
10 A time lag
10 A time lag
Digital output 6
1
5 x 20
12.5 A fast
12.5 A fast
12.5 A fast
12.5 A fast
Refrigerant circuit compartment fan power
supply
1
10.3 x 38
0.5 A AM
0.5 A AM
0.5 A AM
0.5 A AM
Tab. 4.a
4.2 Water connections
Refer to Figure 4.a.
Caution:
before continuing, make sure the unit is powered off,
placing disconnect switch QS1 and the switch or disconnect device on the
HEOS BOX power supply line in the OFF position (see the wiring diagram).
The mains power disconnect device must have a contact opening
distance that allows complete disconnection in overvoltage category III
conditions; it must also be incorporated into the HEOS BOX power supply
line in accordance with national regulations.
To simplify installation and maintenance:
• install a manual shut-off valve immediately before the water inlet to the
unit (the valve is not supplied by CAREL);
• install automatic air vent valves (not supplied by CAREL) in the piping, at
the highest positions in the circuit;
• avoid piping layouts in which water may stagnate when the system is
stopped;