EXAMPLE 3:
Read Property command of the Analog Value Object instance 4 of the same Carel unit described in the above
example.
propertyIdentifier
propertyValue
object-identifier
(Analog -value,4)
object-name
"CAREL ANALOG 00001-01-004"
object-type
2(Analog -value)
present-value
0
status-flags
(FALSE,FALSE,FALSE,FALSE)
event-state
0(normal)
out-of-service
FALSE
units
95 (no-units)
EXAMPLE 4:
Read Property command of the Binary Value Object instance 4 of the same Carel unit described in the above
example.
propertyIdentifier
propertyValue
object-identifier
(Binary-value,4)
object-name
"CAREL BOOL 00001-01-004"
object-type
5(Binary-value)
present-value
0(inactive)
status-flags
(FALSE,FALSE,FALSE,FALSE)
event-state
0 (normal)
out-of-service
FALSE
variable instance
network address
physical device address
variable instance
physical device address
network address