Carel FCP/1 User Manual Download Page 21

FCP manual 

Code +030220391 – rel 1.1 07/11/06 

21

 

 

DIFF differential 

type and Carel supervisor address 

integer var. 7 

Modbus address 

 

 

read/write register 107  

resolution and unit of measure   

1% 

range 

   0 

to 

100 

default 

 

 

 

10 

Parameter used to set the value of the control differential. Expressed as a % of the full scale of the probes used. Only used if configuration by parameter rather than by 
trimmer is enabled. 

The effective value of the differential is internally limited to the value:  

- 100- effective set point 

 

in Direct mode; 

- effective set point   

 

in Reverse mode. 

so as to guarantee that the maximum output is reached. 
 

MIN minimum 

output 

type and Carel supervisor address 

integer var. 8 

Modbus address 

 

 

read/write register 108  

resolution and unit of measure   

1% 

range 

 

 

 

0 to MAX 

default 

 

 

 

30 

Parameter used to set the minimum output value of the controller.  
Expressed as a % of the mains voltage.  
Only used if: configuration by parameter rather than by trimmer is enabled. 
 

 
MAX maximum 

output 

type and Carel supervisor address 

integer var. 9 

Modbus address 

 

 

read/write register 109  

resolution and unit of measure   

1% 

 

 

range 

   MIN 

to 

100 

default 

   100 

Parameter used to set the maximum output value of the controller.  
Expressed as a % of the mains voltage.  
Only used if: configuration by parameter rather than by trimmer is enabled 
 

 
MODE slave 

mode 

type and Carel supervisor address 

integer var. 10 

Modbus address 

 

 

read/write register 110  

resolution and unit of measure   

 

 

range 

   0 

to 

default 

 

 

 

Parameter used to enable slave mode.  

MODE=0  slave mode disabled; normal operation of the controller; 
MODE=1  slave mode 1 enabled; 

MODE=2  slave mode 2 enabled; 
MODE=3  slave mode 3 enabled; 

For a detailed description of operation in the various modes, see the paragraph “Function slave mode”. 

 

 

ALMO 

output in alarm status 

type and Carel supervisor address 

integer var. 11 

Modbus address 

 

 

read/write register 111  

resolution and unit of measure   

range 

   0 

to 

default 

 

 

 

Parameter used to set the value of the output in the event of faulty probe alarms or external alarm.  

ALMO=0 output 0%; 
ALMO=1  output 50%;  
ALMO=2  output 100%.  

 

 

COFH Cut-off 

hysteresis 

type and Carel supervisor address 

integer var. 12 

Modbus address 

 

 

read/write register 112  

resolution and unit of measure   

1% 

range 

   2 

to 

100 

default 

 

 

 

Parameter used to set the amplitude of the activation hysteresis for the Cut-off function. 
Warning: the value of hysteresis must be: 

< effective set point  

 

in Direct mode 

< 100-effective set point 

 

in Reverse mode 

otherwise the conditions cannot exist to set the output to zero. 

Summary of Contents for FCP/1

Page 1: ...FCP 1 regulator with microprocessor control User manual...

Page 2: ...2...

Page 3: ...the plastic parts In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual Do not attempt to open the device in any...

Page 4: ......

Page 5: ...ion 16 6 8 Outside temperature compensation feedforward function 17 6 9 PI control proportional and integral 17 6 10 Slave mode function 18 6 11 Overriding the output 19 6 12 Phase control modes 19 6...

Page 6: ......

Page 7: ...e increased considerably allowing maximum operating flexibility Control set point and differential Two set points are available which can be selected externally so as to be able to differentiate the o...

Page 8: ...e type of load Index of protection The gasket inside and the materials used to make the case guarantee the controller IP54 index of protection Fastening The device is fastened using 4 screws CE mark E...

Page 9: ...be installed so as to ensure normal cooling according to the flow of air Normally if there are no cooling fans it is installed vertically with the cable outlets downwards The temperature of the surfa...

Page 10: ...sponding terminals Loosen each screw and insert the cable ends then tighten the screws and slightly tug the cables to check that they are sufficiently tight To tighten the screws do not use automatic...

Page 11: ...case the meaning of Open and Closed must be reversed If slave mode is enabled the external control signal is 0 10V In this case the controller electrical circuits need to be modified using jumper JA a...

Page 12: ...by dipswitch Two circuit inactive modifiable by dipswitch Cut off inactive modifiable by dipswitch Input B1 Ratiometric pressure probe Input B2 Ratiometric pressure probe Input B3 NTC temperature prob...

Page 13: ...ED indicates that problems have occurred refer to the table below at the end of the operation release the button after a few seconds the LED goes OFF remove the key from the controller LED signal Caus...

Page 14: ...ct 1 reverse Table 6 a c 6 2 Configuring the probes and selecting the range of measurement The values of the set point and differential are always internally expressed as a of the range of measurement...

Page 15: ...nable two circuits ON two circuits both probes B1 and B2 Table 6 a g Associated parameters par Spv Modb range def uom description PB1E D6 6 0 1 1 1 Enable probe B1 0 disabled 1 enabled PB2E D7 7 0 1 1...

Page 16: ...quivalent to the full mains voltage when the control output increases until reaching the maximum value set the output is forced to the maximum possible and remains there until the conditions require a...

Page 17: ...en probe B3 is enabled By default probe B3 is disabled and consequently so is the function Trimmer function MIN Feedforward gain setting 0 to 100 Table 6 a s Associated parameters MIN I8 108 0 to MAX...

Page 18: ...bits plus sign therefore the value 255 corresponds to 100 6 10 Slave mode function The control algorithm is disabled and the output of the controller is directly proportional to input probe B1 in one...

Page 19: ...1 ok STHZ D27 27 0 1 R 1 mains frequency 0 50Hz 1 60Hz Table 6 b d 6 14 Alarm situations and alarm management Alarm status is activated in the event of activation of the thermal protector or in any ca...

Page 20: ...ge 1 to 255 default 1 Parameter used to identify the individual controller so as to make it accessible within the supervision network STP1 set point setpoint1 type and Carel supervisor address integer...

Page 21: ...utput value of the controller Expressed as a of the mains voltage Only used if configuration by parameter rather than by trimmer is enabled MODE slave mode type and Carel supervisor address integer va...

Page 22: ...ed value in systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate DIFF and INTT Only used if PI control is enabled slave mode is no...

Page 23: ...90 The output should be forced to 100 and parameter DLPL set accordingly to reach the maximum fan speed For resistive loads cos fi 1 the displacement should be set to zero Warning the parameter must b...

Page 24: ...d unit of measure 1 range 0 to 100 default Variable used to read the value measured by probe B1 expressed as a of the range of measurement Range of measurement ratiometric pressure probes pressure int...

Page 25: ...INTT I The value calculated is in any case limited as an absolute value by the AWUP parameter The value read is the actual value used in the algorithm expressed in 8 bits plus sign therefore 255 corre...

Page 26: ...gister 5 resolution and unit of measure 0 1 C range T1L to 120 0 default 120 0 Parameter used to set the upper limit of the range of measurement for NTC 50k probes corresponding to 100 The controller...

Page 27: ...enabled The parameter has no meaning if the enabling of the Output saturation function is associated with dipswitch 4 par DIP4 EPIR enable PI control type and Carel supervisor address digital var 5 Mo...

Page 28: ...mains half period The parameter has no meaning if the selection of the type of phase control is associated with dipswitch 4 par DIP4 MOID operating logic of ID1 type and Carel supervisor address digi...

Page 29: ...e used to read the position of dipswitch 3 STD3 0 Off STD3 1 On STD4 dipswitch 4 status type and Carel supervisor address digital var read only 21 Modbus address read coil 21 resolution and unit of me...

Page 30: ...on or short circuit The alarm is only detected if probe B3 is enabled The alarm is not detected if slave mode is selected OKHZ mains frequency reading status type and Carel supervisor address digital...

Page 31: ...R 1 SET trimmer reading tDIF I32 132 0 to 20 R 1 DIF trimmer reading tMIN I33 133 0 to 100 R 1 MIN trimmer reading tMAX I34 134 0 to 100 R 1 MAX trimmer reading PB1R I35 135 0 to 100 R 1 probe B1 rea...

Page 32: ...robe B1 fault alarm 0 inactive 1 active PB2A D24 24 0 1 R 1 probe B2 fault alarm 0 inactive 1 active PB3A D25 25 0 1 R 1 probe B3 fault alarm 0 inactive 1 active OKHZ D26 26 0 1 R 1 mains freq reading...

Page 33: ...e are multiple alarms activated at the same time the first in order shown in the table is signalled The active alarm status forces the output to the value defined by the ALMO parameter The alarm statu...

Page 34: ...ent integer variables relating to parameters I1 I24 integer status variables I31 I42 analogue variables relating to parameters A1 A5 analogue status variables A11 A13 digital variables relating to par...

Page 35: ...variables requested 16 Address of the first variable requested between 101 150 and address of the first variable requested number of variables requested 150 EXCEPTION 3 Address of the first variable...

Page 36: ...te 19200 max length 1 km with shielded cable Signal lights Green power LED Red alarm LED Yellow serial connection active LED flashes when receiving valid frame Controller settings 4 trimmers for manua...

Page 37: ...stics 60 000 operating hours No of automatic operating cycles 100 000 Software class and structure Class A Case Metallic Al with plastic cover ball pressure test 75 C Dimensions 140x135x90 mm Assembly...

Page 38: ...0220391 rel 1 1 07 11 06 38 10 4 FCPM082A10 connections 230 V Fig 10 b L N Controller 230 Vac power supply input L1 N Power supply output to 0 to 230 Vac load Y1 GND Control input 10 5 Dimensions and...

Page 39: ......

Page 40: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency Code 030220391 Rel 1 1 07 11 06...

Reviews: