FCP manual
Code +030220391 – rel 1.1 07/11/06
13
5. Accessories
5.1 Parameter
copying
key
Programming key PSOPZKEY00/A0
The programming keys PSOPZKEY00 (Figure 5.1.a) and PSOPZKEYA0 (Figure 5.1.b) are used to copy the complete set of parameters relating to the CAREL FCP
controller parameters.
The keys must be connected to the PROG KEY connector (4 pin AMP) fitted on the controllers, and work even without switching the controller on (see the summary
diagram in Figure 5.1.c.)
Fig. 5.1.a Fig. 5.1.b Fig. 5.1.c
Two functions are available, and are selected by using the two supplied dipswitches; these can be accessed by removing the battery cover:
- load the parameters for a controller onto the key (UPLOAD - Fig. 5.1.d);
- copy from the key to a controller (DOWNLOAD - Fig. 5.1.e);
Warning: the parameters can only be copied between instruments with the same code. The UPLOAD operation can, however, always
be performed.
Warning: the parameters can only be copied between instruments with the same code and compatible software release.
The UPLOAD operation can, however, always be performed.
The following operations are used for the UPLOAD and/or DOWNLOAD functions, simply by changing the settings of the dipswitches
on the key:
- open the rear cover on the key and position the 2 dipswitches according to the desired operation;
- close the rear cover on the key and insert the key in the connector on the controller;
-
press the button and check the LED: red for a few seconds, then green, indicates that the operation was completed
correctly.
-
Other signals or the flashing of the LED indicates that problems have occurred: refer to the table below;
- at the end of the operation, release the button, after a few seconds the LED goes OFF;
- remove the key from the controller;
LED signal
Cause
Meaning and solution
Red LED flashing
Batteries discharged at start copy
The batteries are discharged, the copy operation cannot be performed. Replace the
batteries.
Green LED flashing
Batteries discharged during copy or at end of
copy
During the copy operation or at the end of the operation the battery level is low. Replace
the batteries and repeat the operation.
Red/green LED flashing (orange signal)
Instrument not compatible
The parameter set-up cannot be copied as the connected controller model is not
compatible. This error only occurs for the DOWNLOAD function; check the code of the
controller and run the copy only for compatible codes.
Red and green LEDs on
Error in data being copied
Error in the data being copied. The instrument's EEPROM is corrupted, and therefore the
key cannot be copied.
Red LED on steady
Data transfer error
The copy operation was not completed due to a serious error when transferring or
copying the data. Repeat the operation, if the problem persists check the key
connections.
LEDs off
Batteries disconnected
Check the batteries.
Table 5.a
5.2
RS485 serial interface board
The RS485 serial interface option (FCSER00000) shown in Figure 5.2.a – is used to connect the instrument to the RS 485 serial network for supervision.
Figures 5.2.b and 5.2.c show the assembly of the interface in the instrument.
Observe the correct polarity of the connector, making sure the protrusion on the serial board matches the notch on the controller, without forcing the board.
Fig. 5.2..a Fig. 5.2.b Fig. 5.2.c
Fig.5.1.e
Fig.5.1.d
Summary of Contents for FCP/1