DP S030220660 rel. 2.3 - 06.12.2021
Duct version variables table
F
unction 04
R
ead Input
R
egister
R
egister
Variable description
D
ata Type
D
efault
S
aved
value
Min.
Value
Max.
value
Min.
range
Max.
range
3x0001
CO2 Value Sampling 4s
Signed 16 Bit
-
-
350
5000
350
5000
3x0002
CO2 Value Sampling 32s
Signed 16 Bit
-
-
350
5000
350
5000
3x0003
RESERVED
-
-
3x0004
RESERVED
-
-
3x0005
Temperature Value Sampling 4s
Signed 16 Bit
-
-
-350
800
-35C
+80C
3x0006
Temperature Value Sampling 32s
Signed 16 Bit
-
-
-350
800
-35C
+80C
3x0007
Relative humidity Value Sampling 4s
Signed 16 Bit
-
-
0
1000
0
100%
3x0008
Relative humidity Value Sampling 32s
Signed 16 Bit
-
-
0
1000
0
100%
F
unction 05
W
rite
S
ingle
C
oil
(1)
R
egister
Variable description
D
ata Type
D
efault
S
aved
value
Min.
Value
Max.
value
Min.
range
Max.
range
0x0001
Reset (Auto zero) CO2
Bit 0
0
NO
0
1
OFF
ON
0x0002
RESERVED
-
-
0x0003
Automatic calibrationCO2
Bit 2
0
YES
0
1
OFF
ON
0x0004
RESERVED
-
-
0x0005
RESERVED
-
-
0x0006
RESERVED
-
-
0x0007
RESERVED
-
-
0x0008
RESERVED
-
-
0x0009
temperature measurement type
Bit 8
0
YES
0
1
°C
°F
F
unction 06
W
rite
S
ingle
R
egister
&
F
unction 16
W
rite Multiple
R
egister
(1)
R
egister
Variable description
D
ata Type
D
efault
S
aved
value
Min.
Value
Max.
value
Min.
range
Max.
range
4x0023
Offset Temperature
Signed 10 Bit
0
YES
-100
100
-10K
+10K
4x0024
Offset Humidity
Signed 10 Bit
0
YES
-100
100
-10%
+10%
F
unction 08
D
iagnostics
S
ub
F
unction
C
ode
P
arameter
D
ata Type
ANSW
E
R
00
Echo of transmission data (Loopback)
Echo data
01
Restart Modbus (Reset listen-only mode)
Echo message
04
Activation listen-only mode
No answer
10
Delete counter
Echo telegram
11
Counter bus telegrams
Unsigned 16 bit
All valid bus messages
12
Counter communication errors (Parity, CRC, frame errors, etc.) Unsigned 16 bit
Faulty bus messages
13
Counter exception messages
Unsigned 16 bit
Error counter
14
Counter slave messages
Unsigned 16 bit
Slave messages
15
Counter messages without answer
Unsigned 16 bit
Broadcast messages (address 0)
F
unction 17
R
eport
S
lave I
D
S
ub
F
unction
C
ode
P
arameter
D
ata Type
ANSW
E
R
00
Number of bytes
Unsigned 8 bit
6
01
Slave ID (device type)
Unsigned 8 bit
AERSGARD® MODBUS
17 = T,H,V,P,C
18 = T,H,V,C
19 = T,H,C
20 = T,H
21 = T,H,P
T: temperature
H: relative humidity
V: air quality (VOC)
P: particulate matter (PM)
C: carbon dioxide (CO2)
02
Slave ID (device class)
Unsigned 8 bit
60 = AERASGARD® / AERASREG®
03
03 Status
Unsigned 8 bit
255 = RUN, 0 = STOP
04
04 Version number (release)
Unsigned 8 bit
1 - 9
05
05 Version number (version)
Unsigned 8 bit
1…99
06
06 Version number (index)
Unsigned 8 bit
1
Tab. 3.h
(1
)
:
“write-only" variables that can be set to the desired value on Modbus supervision systems but their value cannot be read.
For Carel supervisors, these variables are displayed in the "value" field with "***" symbols unless they are set to a new value. In
these cases, the "value" field indicates the number sent in programming to the probe until the next restart.
Summary of Contents for DP
Page 2: ......
Page 4: ......
Page 6: ......
Page 38: ...38 ITA Sensori DP 030220660 rel 2 3 06 12 2021 Installazione sensori DP TH Note ...
Page 40: ......
Page 42: ......
Page 74: ...38 ENG DP Sensors 030220660 rel 2 3 06 12 2021 Notes ...
Page 75: ...39 ENG DPSensors 030220660rel 2 3 06 12 2021 ...