Carbolite MTF 15 Installation, Operation & Maintenance Instructions Manual Download Page 5

 

MTF 9/15 

 

 

C

ONTROLLER 

O

PERATION 

 

4.1  Eurotherm 2132 

 

 

When switched on, the controller lights up, goes through a short test routine, and then displays the 
measured temperature and starts to control. The output light glows or flashes as heating occurs.  

 The 

Page

 key 

 allows access to parameter lists within the controller; most lists and parameters 

are hidden and cannot be accessed by the operator because they contain factory-set parameters 
which should not be changed.  

 

A single press of the page key 

 displays the temperature units, normally set to °C; further presses 

reveal the lists indicated in the Navigation Diagram in section 4.6. 

 The 

Scroll

 key 

4

 allows access to the parameters within a list. Some parameters are display-only; 

others may be altered by the operator. Some parameters only appear in appropriate circumstances 
– for example, working setpoint does not appear if setpoint ramp rate is Off.  

 

A single press of the scroll key 

4

 displays the temperature units; further presses reveal the 

parameters in the current list indicated in the Navigation Diagram.  

 

To return to the Home list at any time, press Page 

 and Scroll 

4

 together, or wait for 45 seconds. 

 The 

Down

 

T

 and 

Up

 

S

 keys are used to alter the setpoint or other parameter values. 

4.2  Basic Operation 

Normally no operator action is required other than entering the setpoint, as the 2132 starts to 
control on being switched on, as described above. 

4.3  Altering the Setpoint  

 

With the display at “home”, showing the measured temperature, press Down 

T

 or Up 

S

 once to 

display the setpoint; press again or hold down to adjust it. The display returns to the measured 
temperature when no key is pressed for 0.5 seconds. 

4.4  Stopping and Starting Control 

It is possible to stop and start the controller without altering the setpoint. Press Scroll 

4

 until the 

legend 

m-A

 (manual/auto) appears. In the 2132, manual means “off” and auto means “on”. Press 

Down 

T

 or Up 

S

 once to show the current on/off state: 

mAn

 for off, and 

Auto

 for on. Press 

T

 or 

S

 to change between manual and auto (off and on) as required. 

 

Note that timer modes 1 & 3 set the controller to 

mAn

 at the end of the timing period. If the 

controller unexpectedly does not control it may be in manual, possibly as the result of previous 
use of the timer function. 

4.5 

MF09 

Summary of Contents for MTF 15

Page 1: ...supply CONTENTS section page 1 0 Symbols Warnings 2 2 0 Installation 3 3 0 Operating Instructions 4 4 0 Controller Operation 5 5 0 Maintenance 10 6 0 Repairs Replacements 11 7 0 Fault Analysis 13 8 0...

Page 2: ...s Heat Light the adjacent light glows or flashes to indicate that power is being supplied to the elements 1 2 Warning Symbols DANGER of electrical shock read any warning printed by this symbol DANGER...

Page 3: ...A C supply with earth ground The supply may be Live to Neutral non reversible Live to Neutral with reversible plug or Live to Live The voltage or range of voltages on which the furnace may be operate...

Page 4: ...e at high temperature when not required The maximum temperature is shown on the furnace rating label and on the back page of this manual Materials such as waxes case hardening compounds melting fluxes...

Page 5: ...in the Navigation Diagram To return to the Home list at any time press Page and Scroll 4 together or wait for 45 seconds The Down T and Up S keys are used to alter the setpoint or other parameter valu...

Page 6: ...nd fig 2 indicate the possible difference between running without and with a ramp to setpoint value depending on the load and the value used 4 6 Navigation Diagram OP Hi SPrr m A w SP Home List Input...

Page 7: ...The timer starts timing immediately At the end of the timing period control switches off i e goes into Manual to allow cooling and End flashes on the display On during the timing period Off from the...

Page 8: ...ameter changes to run Note that the tmr display shows 0 zero during the last minute of timing and also shows 0 when the time has expired The timer light indicates whether timing is still in progress M...

Page 9: ...rrors or other system errors User calibration allows compensation for such errors and the 2132 allows for a user 2 point calibration This setting is password protected to avoid accidental alteration P...

Page 10: ...hroughout the world We also sell spares by mail order A telephone call or fax often enables a fault to be diagnosed and the necessary spare part despatched Each furnace has its own record card at Carb...

Page 11: ...ulletin No 11 and the UK Health and Safety Executive Guidance Note EH46 We can provide further information on request Alternatively our service division can quote for any repairs to be carried out at...

Page 12: ...beads When refixing the wrapped element position the beads just above edge of the metal channel to maximise the clearance between the outer case and the wires 6 6 Solid State Relay Replacement The so...

Page 13: ...ghts glowing on the controller The SUPPLY light is ON The controller may be faulty or not receiving a supply due to a faulty switch or a wiring fault The SUPPLY light is OFF Check the supply fuses and...

Page 14: ...MTF 9 15 CIRCUIT DIAGRAM 8 1 Circuit Diagram heating element thermocouple 2A 2A Re d Re d Blue Blue L N PE controller L N filter SSR pink grey 2 1 3 4 Green Yellow 9 0 14 MF09...

Page 15: ...nd 220 240V models Electronic power limiting in the 2132 controller is used to reduce the power in the 220 240V model The correct power limit settings parameter OP Hi for the furnace are as follows 22...

Page 16: ...l 41 41 541 5877 Fax 41 41 541 5878 Email General Information Sales info kesn ch Accounts Department accounts kesn ch USA O ce 233 Rogue River Highway 425 Grants Pass Oregon 97527 5429 USA Tel 1 503 2...

Reviews: