Programming
16
MC19-1.22
5.14 Program Example 2
The following sequence of entries creates and runs the program shown graphically below.
1.
Turn the Setpoint to ‘0’ by Pressing down
2.
Press page
until Prog, Segments Used is displayed. On P10 and P25 models press up
or down
to select a new program number, (a program with only 1 segment).
3.
Press scroll
until Holdback Value is displayed. Press up
or down
to set to ‘5’
degrees
4.
Press scroll
until Ramp Units is displayed. Press up
or down
to set to ‘Min’
5.
Press scroll
until Cycles is displayed. Default ‘1’
6.
Press scroll
until Segment 1 is displayed
7.
Press scroll
until Segment Type is displayed. Press up
or down
to select ‘Time’
8.
Press scroll
until Holdback Type is displayed. Default ‘Off’
9.
Press scroll
until Target SP is displayed. Press up
or down
to set to ‘600’ degrees
10.
Press scroll
until Duration is displayed. Press up
or down
to set to ’30:00.0’
minutes
Repeat steps 6 to 10 for 4 more segments. Enter the following parameters and values: Note:
Call segments are not available on single program models.
Segment Type Rate
Target SP ‘400’ degrees. Ramp Rate ‘2.0’ degrees per minute
Segment Type Step Target SP ‘200’ degrees
Segment Type Dwell Holdback ‘High’. Duration ’30:00.0’ minutes
Segment Type Call Call Prog ‘next number’. Call Cycles ‘2’
Finish the program with an End segment:
11.
Press scroll
until Segment Type is displayed. Press up
or down
to select ‘End’
12.
Press scroll
until End Type is displayed. Press up
or down
to select ‘Dwell’
Repeat the sequence to create a short program ‘3’ as suggested in the diagram.
13.
Press page
and scroll
together to return to the home display
To run the program either press RUN/HOLD or
14.
Press page
until Program Status is displayed
15.
Press scroll
until the cursor moves to the program status of ‘Reset’
16.
Press
to s
elect ‘Run’
Segment 1
Type ‘Time’
‘Target’ 600°
‘Duration’
30min
Segment 2
Type ‘Rate’
‘Target’ 400°
‘Rate’ 2°C/m
Segment 3
Type ‘Step’
‘Target’ 200°
Segment 5
Type ‘Call’
Call prog 3
Call cycles 2
Segment 6
Type ‘End’
End type
‘Dwell’
400°C
600°C
200°C
2°C/m
30min
Segment 4
Type ‘Dwell’
‘Duration’
30min
‘H’back type’
‘High’
200°C
Program 3
Example
30min
Seg
4
‘
Ho
ld
bac
k
Valu
e’
5
°C
200°C
400°C
P10 and
P25 only
Summary of Contents for 3508 P1
Page 23: ...Navigation 23 MC19 1 20 ...