17
Relative Humidity
– Duct Mount (Return or Discharge)
If a duct mounted humidity sensors is called for in the specifications, follow the instructions in this section.
A duct mounted (return or discharge
duct) humidity sensor (PN: A/RH3-
DO10) shall be installed in the duct of
the RTU.
terminology of the sensor.
A 1” hole
should be drilled in the duct so the
sensor probe can be inserted into the
airstream. The sensor should be
secured to the duct using the
mounting flanges. Ensure that any
holes in the duct are properly sealed.
Use EMT conduit where sensor wiring
would be exposed to the elements
when routing wire back to the
RTULink control board. Standard 18-
5 thermostat wire should be used for
sensor wiring.
The sensor has a bank of eight dip
switches that control the range of the
output voltage of the humidity sensor.
Switches seven (7) and eight (8) need
to be turned ON and the rest should
remain OFF. These dip switches can
be seen in the sensor detail in
mounted humidity sensor that is wired
to the “RTU” Input 1 on the RTULink.
Once the sensor is wired to an input,
enter the configuration menu via the
onboard HMI and configure the
corresponding input for the humidity
sensor that was installed. In the
example in Figure 18, the sensor was
installed in the return duct, so
“RTU IN
1” would be configured for “RA RH”.
Figure 17. Duct Mount Humidity Sensor
Figure 18. RTULink - Duct Mount RH
Summary of Contents for RTULink
Page 2: ...2...
Page 30: ...30 Main Board HMI Menu Tree...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 34: ...34...
Page 41: ...41...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...
Page 52: ...52 APPENDIX C Fixed Dry Bulb Economizer Figure 34 Fixed Dry Bulb Economizer Operation...
Page 53: ...53 Differential Dry Bulb Economizer Figure 35 Differential Dry Bulb Economizer Operation...
Page 54: ...54 Fixed Enthalpy Economizer Figure 36 Fixed Enthalpy Economizer Operation...
Page 55: ...55 Differential Enthalpy Economizer Figure 37 Differential Enthalpy Economizer Operation...