Using the Display Panel
Use of the Display Panel (Figure 5) is described in the following paragraphs.
Figure 5. Display Panel and Functions
CAUTION
Attempting to operate a single Hybrid UPS system while it is connected
to the output of other operating Hybrid UPS systems may cause all
systems to sense a fault condition and stop providing power to the
critical load. Only attempt to operate an individual system if it is isolated
from all other Hybrid UPS system outputs.
The Display Panel is located on the front of the package above the engine air inlet, and is
used to control a selected few operating functions, show individual system status, and
access data stored within the microturbine system. The Display Panel includes a keypad,
a display window, navigation buttons, and system control buttons. The paragraphs below
describe Display Panel operation.
The primary control and configuration interfaces to the Hybrid UPS system are the UPS
Controller and the Capstone Remote Monitoring System (CRMS) software. During normal
operation, the UPS Controller is the MultiPac master for all Hybrid UPS systems
connected to it. In this operating mode, all Hybrid UPS systems are MultiPac enabled and
the control functions of the local Display Panel are limited. When a Hybrid UPS
microturbine is MultiPac disabled, the local Display Panel functionality is somewhat
increased. However, proper operation of the Hybrid UPS microturbine is restricted to
operation when it is isolated from the outputs of all other Hybrid UPS systems and the Grid
Connect and Stand Alone Interlock connections are correctly activated.
Display Panel Areas
The
BATT START
button, at the far left of the Display Panel, is used to wake a Hybrid
UPS system from sleep mode.
The
Numeric Keypad
, located to the left of the Display Window, is for data input. The
system accepts data input only on specific screens, and the input line must be selected,
indicated by the flashing line. Data input from the Numeric Keypad requires logging-on
with a password (refer to
on page 37).
Numeric Keypad
Display Window
Navigation Buttons
Interlock Button
Control Buttons
Battery Wake-Up Button