31/33
1>. Refer to
(→7.6)
2>. If the capillary touch the inner cabinet and the air duct panel, adjust the position of the
capillary and add the incabloc plastic.
7.8.
Oil jammed noise
Fault: intermittent and deep jet noise coming from inside of the capillary.
Cause: Compressor oil flowing into the cooling system pipe work probably due to the
capillary slightly out of alignment during transportation
Solution: Clean the cooling system pipe, vacuumize it and recharge with refrigerant see
(→
7.3)
7.9.
Evaporator freezing.
Because the door seal is not air-proof, or the door is not closed well, cause much water fill in
the cabinet, and the water got frozen when it encounter the cold air, sometimes the ice is too
thick, and it will block the fan or broken the fan.
The solution:
1 >.
Replace the door seal or close the door well. If the door seal is slightly not air-proof, it
can be repaired by the heat dryer.
Aiming at the distortion of the seal with the heat dryer, and move up and down until it expand
to the normal state. When it is cool, check it with the door closed, if there is any distortion,
dry it again until it fix for the door.
(Fig.18)
2 >. If the fan is broken, replace the fan.
Fig.18