L-L 265.00-BM
20 / 24
TECHNICAL SPECIFICATIONS
JUMBO 800
Burner Model
RIELLO R40-N900S
Burner Nozzle
RIELLO G20
Nominal Heat Input
[BTU/h]
800,000
Natural gas
Supply pressure
[in w.c.]
min 7" w.c.
max 10" w.c.
Normal
altitude 0 -
2.000 ft above
sea level
(U.S.A. and
Canada)
Heat input
[BTU/h]
802,180
Manifold pressure
[in w.c.]
2.68
Burner head position
[N°]
5
Burner Air setting
[N°]
5.2
Fuel consumption
[CFH]
772.0
Altitude 2.000
- 4.500 ft
above sea
level (Canada
only)
Heat input
[BTU/h]
721,962
Manifold pressure
[in w.c.]
2.56
Burner head position
[N°]
5
Burner Air setting
[N°]
Max
Fuel consumption
[CFH]
694.80
L.P.G.
Supply pressure
[in w.c.]
min 8" w.c.
max 13" w.c.
Gas firing valve
[in]
0.464
Normal
altitude 0 -
2.000 ft above
sea level
(U.S.A. and
Canada)
Heat input
[BTU/h]
805,499
Manifold pressure
[in w.c.]
2.20
Burner head position
[N°]
5
Burner Air setting
[N°]
5.2
Fuel consumption
[CFH]
317.16
Altitude 2.000
- 4.500 ft
above sea
level (Canada
only)
Heat input
[BTU/h]
724,950
Manifold pressure
[in w.c.]
2.00
Burner head position
[N°]
5
Burner Air setting
[N°]
Max
Fuel consumption
[CFH]
285.44
Air flow
[cfm] 10,005.8
Fan Thermostat Setting
[°F]
95
Burner Thermostat Setting
[°F]
194
Power supply
Phase
1
Voltage [V]
240
Frequency
[Hz]
60
Electric consumption
[W] 3,300
[A] 15.5
Flue diameter
[in]
7.87
Compulsory flue draft
[in]
0.05
Maximum air temperature
[°F]
250
Max. operating pressure elec. gas valve
[psi]
5
Air distribution duct
Max Static pressure
[in]
0.80
Max length 1 way - dia 28”/26"
[ft]
90
Max length 2 ways - dia 24"
[ft]
45
Max length 4 way - dia 18"
[ft]
45
Max length 5 way - dia 14"
[ft]
36
Inlet flexible duct
Max length 1 way - dia 28.8"
[ft]
18
Noise level at 1 m
[dBA]
71
Dimensions. L x W x H
[in]
91.93 x 38.98 x 62.34
Weight
[lb] 773.82