CanProx Proximity/Keypad Reader
Installation Instructions
August 2018 • Rev. 1.6
Page 8 of 14
Programming
P-640-HA & P-620-HA (26-BIT WIEGAND OUTPUT) – APPLICABLE FOR
3RD PARTY AND CANSEC CONTROLLERS
The reader is shipped with the keypad outputting 8-bit burst Wiegand. To change
the keypad output to 26-bit Wiegand, follow the procedure below.
See Appendix for
8-bit burst mode
.
1.
Cycle power to the reader.
2.
Present the Wiegand Keypad Data Mode control card to the reader – reader will
beep four times.
3.
Enter the facility code to be applied to the keypad (FC = 0 to 255); the default
facility code is usually 0. If an unacceptable facility code is entered the reader will
give out one long beep.
4.
Press the “#” key - reader will beep four times to indicate success.
5.
Press the “*” key – reader should beep four times to indicate 26-bit mode is
enabled.
P-640-HA37 & P-620-HA37 (CANSEC 37-BIT WIEGAND OUTPUT) –
APPLICABLE FOR CANSEC CONTROLLERS ONLY
The reader is shipped with the keypad outputting 8-bit burst Wiegand. To change
the keypad output to Cansec 37-bit Wiegand, follow the procedure below.
See
Appendix for 8-bit burst mode
.
1.
Cycle power to the reader.
2.
Present the Wiegand Keypad Data Mode control card to the reader – reader will
beep four times.
3.
Enter the facility code to be applied to the keypad (FC = 0 to 32767); the default
facility code is usually 0. If an unacceptable facility code is entered the reader will
give out one long beep.
4.
Press the “#” key – reader will beep four times to indicate success.
5.
Press the “*” key – reader should beep four times to indicate 37-bit mode is
enabled.