H1000 Elevator Control
Page 6 of 20
Installation Guide
October 2015 • Rev. 1.7
32 FLOOR ELEVATOR SYSTEM
This configuration is used when connecting to an elevator system of up to 32 floors. This
consists of
two
H1000 control panels, designated as a master panel and a slave panel.
Master Panel
Slave 1 Panel
1. Dipswitch Settings:
OPT1:
ON
OPT2:
ON
OPT3:
OFF
OPT4:
OFF
1. Dipswitch Settings:
OPT1:
ON
OPT2:
OFF
OPT3:
OFF
OPT4:
OFF
2. Jumper Setting:
2. Jumper Setting:
3. Address Setting:
3. Address Setting:
Panel address is set to the same as Master Panel
Master
Slave 1
Master and slave RS485 communication wires
RS485 Communication wires to host computer using Cansec
communication line driver, e.g. CLAUSB, Canlan or Air-485
Master Panel:
Controls floor 1 to 16
Slave 1 Panel:
Controls floor 17 to 32
Panel address is set to 1 in this example