background image

 

 

AIR

-485

®

 

Page 8 of 14 

Installation Manual 

November 2014 • Rev. 2.2 

Figure 2: Back 

 

Back: 

1)  RS-485 Input 

– Used for RS-485 communication up- and down-stream. If the 

Air

-485

®

 

modem is connected to a PC using USB, this connection cannot be used.

 

2)  Network ID 

– This is used to set the network ID for the group of 

Air

-485

®

 modems 

communicating together. The Master and corresponding Slaves should all be on the 
same Network ID. Setting the Network ID can be done using the DIP switches, as shown 
in the diagram below:

 

 

 

3)  Signal Strength 

– Signal Strength LEDs indicate the strength of the received signal only 

when DIP switch 7 on the front side of the 

Air

-485

®

 modem is UP (Figure 1).  The rule of 

thumb is that more LEDs are better.  However, as long as you have at least one LED 
and it is on SOLID, there is a solid data connection.  In NORMAL mode, the lower LED 
will be on SOLID and indicates that the unit is powered on.

 

 

Summary of Contents for AIR-485

Page 1: ...AIR 485 INSTALLATION MANUAL November 2014...

Page 2: ...age 2 of 14 Installation Manual November 2014 Rev 2 2 CA AIR485 Important Notice Do not operate the AIR 485 modem with the antenna removed This will cause irreparable damage which is not covered under...

Page 3: ...e surface MOBILE OBSTRUCTIONS Do not locate AIR 485 units where their line of sight to the other unit s can be obstructed by trucks or other mobile equipment TECHNICAL SUPPORT Prior to calling Technic...

Page 4: ...ems are configured through simple DIP switch settings see Figure 1 and 2 on the following pages Long Range Indoor Urban up to 400 m 1 300 feet depending on antenna height and RF interference Outdoor l...

Page 5: ...sive tools and power meters Multiple Network Support Because the range of the Air 485 modems can be up to 10 Km 6 miles line of sight it is possible that installations in close proximity could interfe...

Page 6: ...14 Installation Manual November 2014 Rev 2 2 Setup DIP Switch Settings There are two sets of DIP switches which must be set Figure 1 Front NOTE The RESET button must be pressed whenever a DIP switch s...

Page 7: ...RS 485 bus as Master and set the field units as Slaves 5 Switches 2 and 3 The factory default setting is Low Power If the distance between the Master and Slave s is MORE THAN 100 feet set the switches...

Page 8: ...and corresponding Slaves should all be on the same Network ID Setting the Network ID can be done using the DIP switches as shown in the diagram below 3 Signal Strength Signal Strength LEDs indicate th...

Page 9: ...Outdoor Installation For outdoor applications use the CA AIR485 N which consists of an Air 485 modem and a plastic NEMA enclosure This configuration is temperature rated for 40o C to 85o C 40 F to 18...

Page 10: ...AIR 485 Page 10 of 14 Installation Manual November 2014 Rev 2 2 Wiring Diagrams Wiring H1000 NOTE The EIA RS 485 standard does not permit T Tap or Star connections...

Page 11: ...AIR 485 Page 11 of 14 Installation Manual November 2014 Rev 2 2 Wiring SmartLock NOTE The EIA RS 485 standard does not permit T Tap or Star connections...

Page 12: ...AIR 485 Page 12 of 14 Installation Manual November 2014 Rev 2 2 Typical Air 485 Configuration for SmartLock Air 485 Without CLAUSB or CanLan Air 485 With CLAUSB CanLan on Remote Site...

Page 13: ...Supports maximum 30 panels Supports maximum 16 Air 485 slaves No communications between Air 485 slaves No Air 485 repeaters Works with most 2 wire RS 485 products NOTE The supported baud rates are 48...

Page 14: ...n Rate 115 2 Kbps Receiver Sensitivity 102 dBm 0 00001 BER 115 2 Kbps Transmission Output Power 10 250 500 and 1000 mW Power Requirement USB Power low RF output or 12VDC 1A high RF output Network Topo...

Reviews: