
7
FIG 2
. MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE
TERMINALS, FAN ASSISTED FLUE TERMINALS, ROOM SEALED APPLIANCE
TERMINALS OR THE TERMINALS OF OUTDOOR APPLIANCES.
F
n
b
d
a
k
k
h
h
h
j
e
e
g
c
T
T
T
g
d
j
j
See note 2
See note 3
Openable
window
Door
I
P
M
T = Flue terminal M = Gas meter
I = Mechanical air inlet P = Electricity meter or fuse box
Shading indicates prohibited
areas for flue terminals
Ref Item
Minimum clearances
(mm)
Natural
draft
Fan
assisted
- unless appliance is certified for closer installation
Notes:
1 All distances are measured to the nearest part of the terminal.
2 Prohibited area below electricity meter or fuse box extends to ground level.
3 See clause 5.13.6.6 for restrictions on the
flue terminal
under covered areas.
4 See Appendix J. Figures J2(a) and J3(a), for clearances required from a flue terminal to an
LP
Gas Cylinder
. A
flue terminal
is considered to be a source of ignition.
5 For
appliances
not addressed above acceptance should be obtained from the technical regulator.
Special Note:
This chart shall be read in-conjunction with the full Australian standards.
AS 5601
THE POWER FLUE HEATER IS FAN ASSISTED. SEE COLUMN HIGHLIGHTED
a Below eaves, balconies and other projections:
Appliances
up to 50 MJ/hr input 300 200
Appliances
over 50 MJ/hr input 500 300
b From the ground, above a balcony or other surface 300 300
c From a return wall or external corner 500 500
d From a
gas meter
(M) (see 4.7.11 for vent location of
regulator
) 1000 1000
e From electricity
meter
or fuse box (P) 500 500
f From a drain pipe or soil pipe 150 75
g Horizontally from any building structure or obstruction facing a terminal 500 500
h From any other
flue terminal
, cowl, or combustion air intake 500 500
j Horizontally from an openable window, door, non-mechanical air inlet or other opening into a
building with the exception of sub-floor ventilation:
Appliances
up t 150 MJ/hr input 500 300
Appliances
over 150 MJ/hr input up to 200 MJ/hr input 1500 1500
Appliances over 200 MJ/hr input 1500 1500
All fan assisted
flue appliances
, in the direction of discharge 1500
k From a mechanical air inlet, including a spa blower 1500 1500
n Vertically below an openable window, non-mechanical air inlet, or any other opening into a building
with the exception of sub-floor ventilation:
Space heaters up to 50 MJ/hr input 150 150
Other
appliances
up to 50 MJ/hr 500 500
Appliances
over 50 MJ/hr input and up to 150 MJ/hr input 1000 1000
Appliances
over 150 MJ/hr 1500 1500
REGULATORY LOCATION
22
2. Unplug from wall socket or turn off power at main switchboard if heater
is hard wired.
3. Always shut off the gas supply and ensure that the heater is cool before
commencing any service operations.
4. Always check for gas soundness after servicing.
To replace the primary glass
1. Refer pages 13 and 14, steps 7 to 11, of the installation instructions.
Refit glass and replace in reverse order ensure the inside surface of the
glass is clean and free from finger marks.
Note: ensure the inside surface of the glass is clean and free from finger
marks.
To replace the gas control
To replace the ignition (module) device
1. Unplug wire connectors from ignition module.
2. Remove module mounting bracket by removing
mounting screw.
3. Using pliers bend tabs so that module can come
away from the mounting bracket.
4. Replace ignition device in reverse order.
1. Remove the fascia
2. Unplug the cables from the gas control and disconnect the earth
connection.
3. Disconnect the gas inlet (1/2” compression nut) connection at entry
gas control and the 16mm nut at the outlet of the gas control.
4 . Remove the three M4 screws from the cradle retaining the gas control.
5. Remove gas control.
6 Replace gas control in reverse order and check for gas tightness
Note: check the gas pressure on high and low burner settings. Refer ‘gas
control’, pages 13 and 14
Ignition module
Mounting bracket
General
1. Service work to be carried out by an authorised service person only.
SERVICE INSTRUCTIONS - (DO NOT MODIFY THIS APPLIANCE)
FIG 29.
The Cannon appliance is warranted against defects in materials and
Warranty service, which includes parts and labour for the replacement or
repair of defective parts, is available through the CANNON distributor.
(Details below or on page 24).
Consumers are responsible for service person’s travel outside normal
service areas (approximately seventy (70) kilometer radius from the nearest
Cannon dealer’s location), local transport costs, or any preventative
maintenance works as described in
Any product subjected to misuse, abuse, negligence, accident or alteration
will have its warranty voided. The defacement of serial plate will also void
warranty.
If installation is not carried out in accordance with manufacturer’s
instructions, this warranty may be void.
The customer must keep their “Tax Invoice” as proof of purchase of this
product and compliance certificate as proof of required installation.
workmanship for a period of two (2) years from its date of original
purchase, applicable only for residential use in Australia.
this manual.
Enter the details of the date installed and the Compliance Certificate
number in the appropriate area on the rear page of this manual.