background image

Page - 3 - 

D7292/12 

INSTALLATION AND OPERATING INSTRUCTIONS 

 

These instructions apply to the following Alarm models: 

 

Flameproof audible range, sounder type YO6 

YA60BD, YA60BF, YA60BL, YA60BN    

 

      YA60CD, 

YA60CF, 

YA60CL, 

YA60CN 

 

Flameproof visual range, strobe type V6   5J 

FL60BD50, FL60BF50, FL60BL50, FL60BN50    

      FL60CD50, 

FL60CF50, 

FL60CL50, 

FL60CN50 

      

10J 

FL60BD100, 

FL60BF100, 

FL60BL100, 

FL60BN100 

 

      FL60CD100, 

FL60CF100, 

FL60CL100, 

FL60CN100 

      

20J 

FL60BD200, 

FL60BF200, 

FL60BL200, 

FL60BN200 

 

      FL60CD200, 

FL60CF200, 

FL60CL200, 

FL60CN200 

Combined audible & visual range, type YL6    

YL60BD50, YL60BF50, YL60BL50, YL60BN50    

      YL60CD50, 

YL60CF50, 

YL60CL50, 

YL60CN50 

 

These products are a range of audible and visual alarms approved for use in potentially explosive 
atmospheres, and have been ATEX and IECEx certified by Baseefa Ltd using EN60079-0 and EN60079-
1:2004 standards. 

 

Models are available for use in hazardous areas with the following classifications: Group IIB and IIB+H

2

An alarm approved for use in a particular gas group may be used in areas where the gas group is of a lower 
hazard. 

i.e.  IIB+H

2

  equipment is suitable for Gas groups IIB and IIA, also 

       

       IIB equipment is suitable for Gas group IIA also. 

The alarms are suitable for outdoor use. 

 

 
ALL INSTALLERS MUST PROVIDE SUPPLY LINE FUSES 
 
 

The Yodalex alarms meet the requirements of standards BS EN60529:1992, Degree of protection IP66 
 

General 
The alarms must be installed in accordance with these instructions. 

The alarms must also be installed in accordance with local codes and/or special requirements of any 
authority having jurisdiction. 
 
Models for connection to DC supplies have a DC lines status monitoring facility. 
 
 
 

Summary of Contents for FL60BD100

Page 1: ...2 Tom Cribb Road Thamesmead London SE28 0BH Tel 44 0 20 8316 4477 or 0 20 8317 1717 Fax 44 0 20 8317 2400 Email cliffordandsnell aol com www cliffordandsnell com OPERATING AND INSTALLATION INSTRUCTIONS FOR ATEX AND IECEX YODALEX FLAMEPROOF AUDIBLE AND VISUAL ALARMS D7292 12 ...

Page 2: ... II 2 GD Ex d IIB H2 T 135 C Tamb 20 C to 60 C II 2 GD Ex d IIB H2 T 85 C Tamb 20 C to 40 C These alarms are certified in accordance with the IEC60079 0 2004 Edition 4 and IEC60079 1 2003 Edition 5 The certificate numbers and their associated marking are as follows IECEx BAS05 0086X Ex d IIB T4 Tamb 35 C to 60 C Ex d IIB T6 Tamb 35 C to 40 C IECEx BAS05 0087X Ex d IIB H2 T4 Tamb 20 C to 60 C Ex d ...

Page 3: ...spheres and have been ATEX and IECEx certified by Baseefa Ltd using EN60079 0 and EN60079 1 2004 standards Models are available for use in hazardous areas with the following classifications Group IIB and IIB H2 An alarm approved for use in a particular gas group may be used in areas where the gas group is of a lower hazard i e IIB H2 equipment is suitable for Gas groups IIB and IIA also IIB equipm...

Page 4: ...able cores required by the system arrangement It is preferable that the cable and its seal be fitted at the factory or approved workshop however the method for assembling the cable and sealed components is described below IMPORTANT THE ALARM IS A PRECISION INSTRUMENT TAKE EXTREME CARE WHEN HANDLING Particular care is needed when removing or replacing components which form part of the flameproof en...

Page 5: ...ed stopping plug is fitted by manufacturer as standard The terminals accept wires of 2 5 mm The PCB assembly may be lifted in its slide channels to give easier access to the terminals SOUND SIGNAL SELECTION It is preferable if the sound signal selection is set at the factory or at an approved workshop To make the sound signal selection refer to the table of sound signals and the switch positions f...

Page 6: ...lock washers and flat washers Check that the bracket is tightly secured to the alarm enclosure The fixings for the alarm to the mounting surface are two holes 8 5mm 0 33in on 75mm 2 95in centres Suitable bolts not supplied for securing should be used INTERCONNECTION OF ALARMS Alarms may be connected in parallel that is up to ten alarms with common supplies may be connected as a single system loop ...

Page 7: ...nsumption of 220 mA for 24VDC 135mA for 48VDC 90 mA for 115 VAC and 45 mA for 230 VAC 24VDC 48VDC 115VAC 230VAC 5 JOULES 220mA 130mA 90mA 45mA 10 JOULES 500Ma 300mA 105mA 53mA 20 JOULES 1 1A 500mA 260mA 170mA WARNING POSSIBLE ELECTROSTATIC RISK The Horn and Lens may become electro statically charged and should not be touched or rubbed when in operational service If cleaning is required follow the ...

Page 8: ...0 1 25 0 0 0 0 1 17 Interrupted tone 1000 0 5 1 1 1 1 0 18 Interrupted tone 2500 0 25 0 1 1 1 0 19 Interrupted tone 2500 0 5 1 0 1 1 0 20 Interrupted tone 700 6 12 0 0 1 1 0 Pre vital Message SWEDEN 21 Interrupted tone 1000 1 0 1 1 0 1 0 22 Interrupted tone 700 4 0 0 1 0 1 0 Air raid Alarm SWEDEN 23 Interrupted tone 700 0 25 1 0 0 1 0 Local Warning SWEDEN 24 Interrupted tone 720 0 7 0 3 0 0 0 1 0 ...

Page 9: ...AC ALARM CONNECTION AND SOUND SIGNAL SELECTION D7292 12 Page 9 ...

Page 10: ...time with the Sounder and or Flasher only working when a ring tone is detected on the telephone input Note The Sounder will follow the ring tone whilst the the Flasher will remain flashing only switching Off 4 seconds after the Telephone has been answered Not suitable for UL applications D7292 12 Page 10 ...

Page 11: ...AC ALARM CONNECTION FOR 10 20J BEACONS DC ALARM CONNECTION FOR 10 20J BEACONS D7292 12 Page 11 ...

Page 12: ... 0v Sounder Strobe Sounder 24v dc Earth Strobe 24v dc LK2 removed link 24v dc LK1 link 0v On other side of PCB On other side of PCB Earth Connection 4 3 2 TB3 1 3 4 TB2 2 Sound Selection Pressure Unit Connector x TB1 1 4 3 2 1 Strobe 0v Sounder 24v dc Earth LK2 link 24v dc LK1 link 0v On other side of PCB On other side of PCB resistor E O L Earth Connection 4 3 2 TB3 1 3 4 TB2 2 Sound Selection Pr...

Page 13: ...he first stage sounds by supplying volts to a unit via control switch x This switch remains on and the second stage signal is controlled by switching volts to the third terminal via switch y On other side of PCB Sound Selection On other side of PCB Pressure Unit Connector Earth Connection 4 TB3 3 2 1 4 TB2 3 2 1 4 3 2 TB1 1 Earth LK2 link 24v dc LK1 link 0v To Next Sounder Strobe x y Sounder Strob...

Page 14: ...hes for 2 nd stage of sound alarm link TB2 3 to TB1 2 Line monitoring by supply reversal Select alarm stage 1 on SW1 Select alarm stage 2 on SW2 Common supply to Sounder and Strobe On other side of PCB Sound Selection On other side of PCB Pressure Unit Connector Earth Connection 4 TB3 3 2 1 4 TB2 3 2 LK2 removed link 24v dc 1 4 3 2 TB1 1 Earth LK1 link 0v To Next Sounder x to next strobe 0v Sounde...

Reviews: