TAMPER SWITCH  (Continued)

CMD IN / REMOTE LED INPUT

Use DIP switch S2-3 to select the function of the control input at
terminal strip TB2. Designate the input as a Command Input or a
Remote LED Enable.  The input circuit is shown in Figure 7.

As Command Input:  a logic low signal will initiate a complete
self-test sequence.  If the test fails, the Trouble Output will be
activated.

As a Remote LED Enable:  A logic low signal will enable both
LED's.  The manual LED enable at DIP switch S2-2 must be
OFF.

Note:  If not used, you can leave the input unconnected.

FG-1025Z CONFIGURATION  (Continued)

Tamper
Cavity

.385 in

(9.78 mm)

   #8 or #10
     Screw
(M 4 or M 5)

Rear
Housing

Install screw to seat in tamper
cavity

Figure 5

Figure 7
Command/Remote
LED Input Circuit

High-Impedance

10K

+5V

100K

+5V

ACTIVE LOW

INPUT LOW:
INPUT HIGH: 3.5-5V

0-1.5V

TB2

CMD-IN/

Remote LED

Terminal

TROUBLE OUTPUT

Failure of a power-up or periodic self-test is signaled by a logic
high output at the Trouble Output terminal on TB2.  The output
will be held high until a subsequent self-test passes.  The output
circuit is shown in Figure 8.

FG-1025Z CONFIGURATION

Configure DIP switch S2 to best suit the application:

Figure 8
Trouble Output
Circuit

TB2

Trouble Output Terminal
20 mA/16 V max
Active High

S2

ON

LATCH

LED

CMD-IN

1

2

3

REMOTE
    LED

Shaded boxes are factory default settings.

a

Latched alarm LED does not affect timing of alarm relay.

b

Reset the alarm LED by removing and restoring power, or by

 toggling the S2 LATCH switch off and on.

c

Sets function of CMD-IN/Remote LED terminal.

SWITCH

OFF

ON

LATCH

Red alarm LED

Red alarm LED

lights for 5 seconds

latches ON when

when unit alarms

unit alarms

a,b

LED

LEDs are disabled

LEDs are enabled

except during
power-up test

CMD IN/

TB2 terminal set to

TB2 terminal set to

REMOTE

Remote LED Enable

c

Command Input

c

LED

TESTING

The FG-1025Z should be tested at least once each year.  Test
the unit with the FG-701 Glass-Break Simulator.  The model FG-
700 Glass-Break Simulator can be used if it is set for the
TEMPered glass sound.  Other glass-break simulators will not
give accurate indication of range.

You must place the FG-1025Z in Test Mode before you can test
the unit.

To activate Test Mode:

1. Stand inside the protected zone within 10 feet (3 m) of the

unit.

NOTE: The FG-1025Z will not respond to simulator sounds from
the excluded zone.

2. Switch the FG-701 to ACTIVATE and MANual modes.
3. Point the front of the simulator at the unit and press the red

start button.  (See Figure 9.)

You should hear a short buzz from the simulator, and the green
LED on the FG-1025Z should begin flashing about once per
second to indicate it is in Test Mode.

NOTE: In Test Mode the LED disable switch is overridden.

Figure 9

Red Start
Button

Glass-Break

Detector

Summary of Contents for FG-1025Z

Page 1: ...o the Technical Information section on page 5 MOUNTING LOCATION For the greatest flexibility in aiming the FG 1025Z mount the unit on the ceiling Figure 3 illustrates the protected excluded and keepout zones for a ceiling mounted FG 1025Z The arrows printed on the intermediate cover see Figure 1 indicate the direction of the protected zone Refer to the Mounting Guidelines to select an appropriate ...

Page 2: ...h of the room as possible should be in the excluded zone There is no minimum range but the unit must have a clear line of sight and a clear view of the protected glass The preferred location is on the ceiling directly opposite the glass Do not mount in corners and keep the unit at least 1 0 3 m from any adjacent walls When wall mounting mount the unit at a height of at least 6 feet 1 8 m to avoid ...

Page 3: ... S2 ON LATCH LED CMD IN 1 2 3 REMOTE LED Shaded boxes are factory default settings a Latched alarm LED does not affect timing of alarm relay b Reset the alarm LED by removing and restoring power or by toggling the S2 LATCH switch off and on c Sets function of CMD IN Remote LED terminal SWITCH OFF ON LATCH Red alarm LED Red alarm LED lights for 5 seconds latches ON when when unit alarms unit alarms...

Page 4: ...ON one second ON one second Trouble detected Flash ON OFF Flash OFF ON Test mode no alarm Flash once per second OFF Test mode event detected Flicker OFF Test mode alarm Flash once per second ON LED Indicators The two LED s on the front cover are used to indicate the sensor s operational status The following table summarizes the LED operation when the LED s are enabled APPLICATIONS INFORMATION The ...

Page 5: ...e is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between...

Page 6: ... anyone for any consequential or incidental damages for breach of this or any other warranty express or implied or upon any other basis of liability whatsoever even if the loss or damage is caused by Seller s own negligence or fault Seller does not represent that its product may not be compromised or circumvented that the product will prevent any personal injury or property loss by burglary robber...

Reviews: