background image

Any  data,  descriptions  or  specifications  presented  herein  are  subject  to  revision  by  C&D 

Technologies,  Inc.  without  notice.  While  such  information  is  believed  to  be  accurate  as 

 

indicated  herein,  C&D  Technologies,  Inc.  makes  no  warranty  and  hereby  disclaims  all 

warranties,  express  or  implied,  with  regard  to  the  accuracy  or  completeness  of  such 

 

information.  Further,  because  the  product(s)  featured  herein  may  be  used  under  conditions 

beyond  its  control,  C&D  Technologies,  Inc.  hereby  disclaims  all  warranties,  either  express  or 

implied, concerning the fitness or suitability of such product(s) for any particular use or in any 

specific application or arising from any course of dealing or usage of trade. The user is solely 

responsible for determining the suitability of the product(s) featured herein for user’s intended 

purpose and in user’s specific application.
Copyright 2014  C&D TECHNOLOGIES, INC.     Printed in U.S.A.     RS02098    0114/CD

1400 Union Meeting Road

P.O. Box 3053 • Blue Bell, PA 19422-0858

(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630

[email protected]

www.cdtechno.com

End to End Rack Installation Instructions:

Where a continuous rack string is required, two racks may be 

installed adjacent in length.

Frame Location: 

End to end rack assemblies are installed as two individual, stand-

alone rack assemblies as shown. When installing standard racks, 

there is no minimum clearance between racks (they can be abutted). 

When installing EP racks the two racks must be spaced apart so that 

the minimum distance between the ends of the restraint rails is 5”. 

If the support rails are fully packed with cells, the end restraint rails 

may extend beyond the support rails. In such an instance, the 5” 

clearance dimension should be applied to the corner brackets. 

See Figure 16.

RACK LABEL:
Place the IBC certification label (one (1) supplied with rack) on a 

frame upright. Select a frame upright that is readily viewable. See 

Figure 17.

TOUCH UP PAINT:
Touch up paint (C&D part number RH00289) is available through separate purchase. Contact C&D rep for more details.

ADDITIONAL INSTRUCTIONS FOR MULTI-RACK ARRANGEMENTS

FIGURE 16

End to End Installation

FIGURE 17

Rack Label Placement

End Rail within Support Rails

End Rail beyond Support Rails

Summary of Contents for RDC Series

Page 1: ...e codes Do not attach rack to walls without consulting the appropriate structural engineer Mounting holes are provided in the base of each frame All frames must be secured to floor using all anchor bo...

Page 2: ...vide floor mounting hardware SEE PAGE 7 8 FOR LOCATION OF MULTI RACK ARRANGEMENTS 4 Initial Assembly Anchor bolt washers P N RD05084 or RD05100 for three tier racks are supplied with the EP racks Each...

Page 3: ...NSTRUCTIONS FOR RDC STANDARD AND EP RACKS 6 Leveling Check that the rack is level and square Torque down all bolts First torque the cross brace bolts to 55 65 ft lb 75 88 N m then torque the rail to f...

Page 4: ...ount of water unscented talcum or Dow Corning III may be applied to the rail cover to help reduce friction For rows having an odd number of batteries the center of the first battery installed will mat...

Page 5: ...d Cover Serrated Nut Corner Bracket Assembled Side Restraint Rail and Cover Support Rail and Cover End Restraint Rail and Cover End Rail Restraint Rail s and Corner Brackets assembly is reversed the e...

Page 6: ...cable assemblies as determined by the battery arrangement Refer to Battery Installation Manual RS 1476 for more detail on battery connection and initialization charge Follow Battery Installation Manu...

Page 7: ...anchor bolt slots with a 1 06 x 0 69 26 9 mm x 17 5 mm for One Tier and Two Step rack models and a 1 06 x 0 81 26 9 mm x 20 6 mm for Two Tier and Three Tier rack models The distance between the anchor...

Page 8: ...19 7899 800 543 8630 customersvc cdtechno com www cdtechno com End to End Rack Installation Instructions Where a continuous rack string is required two racks may be installed adjacent in length Frame...

Reviews: