Any data, descriptions or specifications presented herein are subject to revision by C&D
Technologies, Inc. without notice. While such information is believed to be accurate as
indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all
warranties, express or implied, with regard to the accuracy or completeness of such
information. Further, because the product(s) featured herein may be used under conditions
beyond its control, C&D Technologies, Inc. hereby disclaims all warranties, either express or
implied, concerning the fitness or suitability of such product(s) for any particular use or in any
specific application or arising from any course of dealing or usage of trade. The user is solely
responsible for determining the suitability of the product(s) featured herein for user’s intended
purpose and in user’s specific application.
Copyright 2014 C&D TECHNOLOGIES, INC. Printed in U.S.A. RS02098 0114/CD
1400 Union Meeting Road
P.O. Box 3053 • Blue Bell, PA 19422-0858
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630
www.cdtechno.com
End to End Rack Installation Instructions:
Where a continuous rack string is required, two racks may be
installed adjacent in length.
Frame Location:
End to end rack assemblies are installed as two individual, stand-
alone rack assemblies as shown. When installing standard racks,
there is no minimum clearance between racks (they can be abutted).
When installing EP racks the two racks must be spaced apart so that
the minimum distance between the ends of the restraint rails is 5”.
If the support rails are fully packed with cells, the end restraint rails
may extend beyond the support rails. In such an instance, the 5”
clearance dimension should be applied to the corner brackets.
See Figure 16.
RACK LABEL:
Place the IBC certification label (one (1) supplied with rack) on a
frame upright. Select a frame upright that is readily viewable. See
Figure 17.
TOUCH UP PAINT:
Touch up paint (C&D part number RH00289) is available through separate purchase. Contact C&D rep for more details.
ADDITIONAL INSTRUCTIONS FOR MULTI-RACK ARRANGEMENTS
FIGURE 16
End to End Installation
FIGURE 17
Rack Label Placement
End Rail within Support Rails
End Rail beyond Support Rails