![CanadianSolar CSI-50K-T400GL03-E Installation And Operation Manual Download Page 33](http://html1.mh-extra.com/html/canadiansolar/csi-50k-t400gl03-e/csi-50k-t400gl03-e_installation-and-operation-manual_4079493033.webp)
.65.
.64.
10. Specifications
Model
CSI-50K-T400GL03-E
10. Specifications
Model
CSI-60K-T400GL03-E
Dimensions (W*H*D)
Weight
691*578*338mm
54.5kg
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
1100
5*32
5*50
5/10
0.8leading~0.8lagging
50/60
98.7%
98.3%
Transformerless
<
1W
-25
℃...
+60
℃
0~100%
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
600
50000
55000
55000
76.0/72.2
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
Max. output current (Amps)
83.6
3/N/PE, 220/380, 230/400
Rated grid output current (Amps)
Dimensions (W*H*D)
Weight
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
1100
6*32
6*50
6/12
0.8leading~0.8lagging
50/60
98.7%
98.3%
Transformerless
<
1W
-25
℃...
+60
℃
0~100%
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
600
60000
66000
66000
91.2/86.6
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
Max. output current (Amps)
100.3
3/N/PE, 220/380, 230/400
Rated grid output current (Amps)
691*578*338mm
54.5kg
AC connection
DC connection
Display
Communication connections
MC4 connector
OT Terminal (max 70 mm²)
LCD, Capacitive touch buttons
RS485, Optional: Wi-Fi, PLC
Ingress protection
Cooling concept
Max.operation altitude
IP66
Intelligent redundant cooling
4000m
AC connection
DC connection
Display
Communication connections
MC4 connector
OT Terminal (max 70 mm²)
LCD, Capacitive touch buttons
Ingress protection
Cooling concept
Max.operation altitude
IP66
Intelligent redundant cooling
4000m
RS485, Optional: Wi-Fi, PLC