Select grid standard (Figure 7.24)
7.5.1 Select Grid Standard
NOTE:
The "User-Def" function can be only used by the service engineer and changing
protection level must be allowed by the local grid company.
NOTE:
This is for service technicians only. The inverter is customized according to the
local standard before shipping, there should be no requirement to set the
standard.
7.5 Advanced Settings - Technicians Only
Select Advanced Settings from the Main Menu to access the following options:
NOTE:
This function is for authorised technicians only. Improper access and operation
may result in abnormal results and damage to the inverter.
Password this function is for authorised technicians only.
Password
(
refer to 7.4 section
)
required – restricted access – authorised
technicians only.
Un-authorised access may void the warranty.
The
default
password
is
"
0010
".
Figure 7.23 Advanced settings
Advanced
Set
.
2015-02-23 19 35
Select
Standard
Grid
ON
/
OFF
Power Control
Clear
Energy
Restore
Settings
Calibrate
Reset
Password
7. General Operation
7. General Operation
Press the UP/DOWN keys to select the standard (AS4777,VDE4105,UL-1741, G59/3,
CQC and “User-Def” function).Press the ENTER key to confirm the setting. Press the
ESC key to cancel changes and returns to previous menu.
Selecting the User-Def submenu will access to the following submenu (see Figure 7.25):
Figure 7.24 Select national standards
Figure 7.25 User-Def
Select Standard
2015-02-23 19 35
Select
Standard
G59/3
E S C
U P
D O W N
E N T
Y E S
=
< E N T >
N O
=
< E S C >
User
-
Def
2015-02-23 19 35
OV
-
G
-
V1
:
OV
-
G
-
V2
:
UN-G-V1
:
UN-G-V2
:
OV-G-F1
:
OV-G-F2
:
UN-G-F1
:
UN-G-F2
:
Startup
-
T
:
440V
459V
330V
299V
51.0Hz
52.0Hz
48.0Hz
47.0Hz
060s
OV
-
G
-
V1
-
T
:
OV
-
G
-
V2
-
T
:
UN
-
G
-
V1
-
T
:
UN
-
G
-
V2
-
T
:
OV
-
G
-
F1
-
T
:
OV
-
G
-
F2
-
T
:
UN
-
G
-
F1
-
T
:
UN
-
G
-
F2
-
T
:
Restore
-
T
:
1
.
0s
0.2s
1
.
0s
0.2s
1
.
0s
0.2s
1
.
0s
0.2s
060s
S
E L E C T
=
< E N T >
D
O N E
=
< E S C >
.38.
.39.