4.3 DC Cable Connection 

 

 

DANGER

     

Electric shock! 
The PV array will generate lethal high voltage once exposed to sunlight. 
Before  performing  electrical  operations,  ensure  that  all  cables  are  uncharged. 
Do not turn on the AC circuit breaker before the inverter is electrically connected. 
Ensure that the DC switch of the inverter is set to OFF.

 

4.3.1 Connection Procedure     
Step 1:   Strip the insulation from each DC cable by 7mm. 
Step 2:   Assemble the cable ends with the crimping pliers 
Step 3:   Lead the cable through cable gland, and insert into the insulator until it snaps into place. 
 

  Gently pull the cable backward to ensure firm connection. Tighten the cable gland and 

the insulator (torque 2.5 N.m to 3 N.m). 

Step 4:   Check for polarity correctness. 
 

  The inverter will not function properly if any PV polarity is reversed. 

7

正极端子

负极端子

锁紧螺母

正极外壳

光伏电缆

压接好的端子

密封圈

锁紧螺母

负极外壳

压接好的端子

密封圈

7

PV Cable

Positive
Crimp
Contact

Negative
Crimp
Contact

Press nut

Positive Housing

Seal Ring

Crimped Contact

Press nut

Negative

Seal Ring

Crimped Contact

Housing

固定不动

顺时针转动

专用扳手(x2)

Fixed

Clockwise Rotation

Special Wrench(x2)

 

FIG  4-7  DC  connector  assembly

 

Step 5:   Insert the completed DC connector into the corresponding DC connector input terminal of the inverter. Do not remove 

the  sealing  plug  on  the  input  end  of  the  vacant  DC  connector  on  the  inverter  to  ensure  reliable  protection.  The 
connection steps are as follows

 

OFF

V

~

V

mV

O

A

~

mA

~

~

V

999.9

ON

OFF

 

FIG  4-8  DC  cables  connection   

 

NOTICE

 

If  the  DC  input  power  cable  is  reversely  connected  and  DC  switches  are  set  to  ON,  do  not 

immediately  turn  off  the  DC  switches  or  reconnect  the  positive  and  negative  connectors. 

Otherwise, the device may be damaged. The caused device damage is not covered under any 

warranty. Wait until the solar irradiance declines at night and the PV string current reduces to 

below 0.5 A. Then, turn off the three DC switches, remove the positive and negative connectors, 

and rectify the connection of the DC input power cable. 

 

 

4.4 Communication Cable Connection

 

This series of models provides standard wireless communication function and optional wired communication function.

 

4.4.1 RS485 communication cable connection (Optional)   
 
 

Summary of Contents for CSI-15K-T4001A-E

Page 1: ...QI V02a December 2023 CSI Solar Co Ltd CSI 15K T4001A E CSI 17K T4001A E CSI 20K T4001A E CSI 23K T4001A E CSI 25K T4001A E PV Inverter Quick Installation Guide Part No 91000517 Release Date December...

Page 2: ......

Page 3: ...ce or at the end of this guide to obtain an electronic copy of the manual 5 All operations on this series of products must be completed by professional technicians Professional and technical personnel...

Page 4: ...technical support department on the use of inverters in special climates i e salt sulfur or ammonia areas which may affect the product warranty 6 Prevent the inverter from direct exposure to sun rain...

Page 5: ...during the operation to prevent device damage from colliding with walls or obstacles Step 4 Use one safety bolt to fix left side of inverter to ensure the inverter is fixed to the wall firmly FIG 3 4...

Page 6: ...embled plug into the AC socket on the inverter please refer to the FIG 4 4 Tighten the connection by aligning the arrow on the plug with the circular hole on the socket NOTE Please use the hex wrench...

Page 7: ...system should be grounded for example brackets of PV modules and inverter enclosure When there is only one inverter in the PV system connect the additional grounding cable to a nearby grounding point...

Page 8: ...Ring Crimped Contact Housing x2 Fixed Clockwise Rotation Special Wrench x2 FIG 4 7 DC connector assembly Step 5 Insert the completed DC connector into the corresponding DC connector input terminal of...

Page 9: ...ion RS485A IN RS485B IN GND 5V RS485A OUT RS485B OUT 5V COM 2 COM 3 COM 1 GND FIG 4 10 Assembling the Connector FIG 4 11 Insert the connector into the receptacle 4 4 2 Multi inverter communication sys...

Page 10: ...h if applicable between the inverter and the grid Step 3 Connect the DC switch if applicable between the inverter and the PV string Step 4 Set initial protection parameters via the CSI Smart Energy Ap...

Page 11: ...ongle is connected to the inverter and powered on 2 The distance between the mobile phone and the dongle should be within 5m and there is no shelter 3 Make sure the Bluetooth of your phone is turned O...

Page 12: ...uired on the boot page Notice Must select the correct gird code where the inverter is installed If the gird code is not suitable it may cause the inverter to report a fault error You can also set the...

Page 13: ...EN Rev QI V02a December 2023 CSI Solar Co Ltd 11 11 6 4 Function List 7 Obtaining User Manual Please scan the QR code for more detailed information in user manual...

Reviews: