6. Normal operation
6. Normal operation
.49.
.48.
YES=<ENT> NO=<ESC>
Power
Factor
:+
1
.
00
Figure 6.23 Fixed-PF
Figure 6.24 PF Range
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
7.VgWatt-UL
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for UL1741SA Standards.
Figure 6.26 VgWatt-UL
Voltage1
:
254V
P
-
Limit1
:
100
%
100
%
of
Input
Power
Vmin
Vnom
Vstart
Vstop
Vmax
AC Volt
0
Figure 6.25 Volt
-
Watt
characteristic
Default Settings for UL1741SA:
Rated 480V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (277-333V) Default305V
V4 (Vstop): (305-360V) Default 333V
P1:100% P2:100% P3: 100% P4:0%