environment to avoid direct sunlight and moisture. If 
modules  are  stored  in  an  uncontrolled  environment, 
the  storage  time  should  be  less  than  3  months  and 
extra  precautions  should  be  taken  to  prevent 
connectors from being exposed to moisture or sunlight, 
like using connector endcaps. . Connector endcaps are 
available upon request. 

 

When  unloading  module  pallets  from  containers, 
please use a fork lift to remove the module pallets and 
the  forklift should  be  close  to  the ground  in  order  to 
avoid the top of module pallets touching the top of the 
cabinet door. The thickness of forklift teeth should be 
less  than  75mm  and  the  length  of  the  forklift  teeth 
should be more than 2300mm. 

 

Unpack  module  pallets  carefully,  following  the  steps 
shown on the pallet. Unpack, transport and store the 
modules with care. 

 

Modules must always be unpacked and installed by two 
people. Always use both hands when handling modules 
with gloves. 

 

 

Do not

 lift modules by their wires or junction box, lift 

them by the frame. 

 

Do not

 place excessive loads on the module or twist the 

module. 

 

Do not 

carry modules on your head. 

 

Do  not

  drop  or  place  objects  (such  as  tools)  on  the 

modules. 

 

Do not 

use sharp instruments on the modules. 

 

Do not

 leave modules unsupported or unsecured. 

 

Do  not

  stand,  step,  walk  and/or  jump  on  modules 

under  any  circumstances.  Localized  heavy  loads  may 
cause  severe  micro-cracks  at  cell  level,  which  in  turn 

may compromise module reliability and void Canadian 
Solar’s warranty. 

 

 

Do not

 change the wiring of bypass diodes. 

 

Keep all electrical contacts clean and dry at all times.   

 

Do not

 expose the modules and its electrical contacts 

to  any  unauthorized  chemical  substance  (e.g.  oil, 
lubricant, pesticide, etc.). 

PRODUCT IDENTIFICATION 

Each  module  has  three  identical  barcodes  (one  in  the 
laminate  under  the  front  glass,  the  second  on  the  rear 
side of the module and the third on the frame) that act as 
a  unique  identifier.  Each  module  has  a  unique  serial 
number containing 14 digits. 

A nameplate is also affixed to the rear of each module. 
This nameplate specifies the model type, as well as the 
main electrical and safety characteristics of the module. 

5.0 MODULE INSTALLATION 

PRECAUTIONARY 

MEASURES 

AND 

GENERAL SAFETY 

 

Prior to installing modules, please obtain 

information  about  any  requirements  and  necessary 
approvals for the site, installation and inspection from 
the relevant authorities. 

 

Check  applicable  building  codes  to  ensure  that  the 
construction  or  structure  (roof,  facade,  support,  etc.) 
can bear the module system load. 

 

Canadian  solar  modules  have  been  qualified  for 
Application  Class  A  (equivalent  to  Safety  Class  II 
requirements). Modules rated under this class should 
be used in systems operating at voltage above 50V or 
power  above  240W,  where  general  contact  access  is 
anticipated. 

Summary of Contents for CS3K-265PB- AG

Page 1: ...For professional use only INSTALLATION MANUAL OF BIFACIAL MODULE...

Page 2: ...CHANICAL ELECTRICAL SPECIFICATIONS 4 4 0 UNPACKING AND STORAGE 5 5 0 MODULE INSTALLATION 6 5 1 MODULE WIRING 8 5 2 GROUNDING 11 6 0 MOUNTING INSTRUCTIONS 12 6 1 MOUNTING METHODS FOR FRAMED BIFACIAL MO...

Page 3: ...sis 1 2 LIMITATION OF LIABILITY Canadian Solar shall not be held responsible for damages of any kind including without limitation bodily harm injury or damage to property in connection with handling P...

Page 4: ...ration above 0 1 weight by weight The copper ribbons used in our solar modules to interconnect solar cells use a thin solder coating layer that contains lead CAS no 7439 92 1 Under normal or reasonabl...

Page 5: ...ing fuse rating The maximum string fuse ratings can be found in ANNEX A Mechanical and Electrical Ratings for all the certified Canadian Solar bifacial module types The minimum string fuse rating for...

Page 6: ...Do not stand step walk and or jump on modules under any circumstances Localized heavy loads may cause severe micro cracks at cell level which in turn may compromise module reliability and void Canadi...

Page 7: ...nditions Part 2 1 Environmental conditions appearing in nature Temperature and humidity Please consult the Canadian Solar technical support department for more information on the use of modules in spe...

Page 8: ...hat specific installation site The highest yields are achieved when sunlight shines perpendicularly onto the PV modules AVOID SHADING Even minor partial shading e g from dirt deposits reduces yields A...

Page 9: ...e In case where a cable connection method not included in below table is used please confirm suitable cable length with Canadian Solar s sales representative Table 2 System Cable Scheme for CS3W CS3U...

Page 10: ...1400 mm jumper cable CS3Y CS6W Cable length 410 mm 290 mm 2000 mm jumper cable Note Modules in adjacent rows need to be rotated 180 degrees for proper installation Portrait installation one row Leap...

Page 11: ...resistant cable ties Protect exposed cables from damage by taking appropriate precautions e g placing them inside a metallic raceway like EMT conduit Avoid exposure to direct sunlight A minimum bendi...

Page 12: ...mplying with UL 1703 or UL 61730 and IEC 61215 2 2016 a safety factor of 1 5 should be applied for calculating the equivalent maximum authorized design loads Project design loads depend on constructio...

Page 13: ...bolt length should be chosen based on actual module frame height For bifacial module with 30 mm frame height our recommended maximum bolt length is 20 mm in order to properly insert the bolts through...

Page 14: ...four holes installation method B Installation Method Module Types Inner four holes installation method A Inner four holes installation method B Middle four holes installation method A Middle four hol...

Page 15: ...of support structure The mounting rails shall be designed to limit as much as possible shade on module rear side cells Canadian Solar s warranty may be void in cases where improper clamps or unsuitabl...

Page 16: ...frame Module Types Max Mechanical Load Pa 3600 2400 5400 2400 5400 3600 A Range mm CS3K 270 380 CS3U 410 490 CS3W 410 490 CS3Y 300 600 400 550 CS6W 300 600 400 500 6 2 2 Clamp mounting on short side o...

Page 17: ...Co Ltd www csisolar com 6 2 3 Clamp mounting on long side of frame and rails parallel to the long side frame Module Types Max Mechanical Load Pa 3800 3200 4000 3200 4400 3200 4400 3600 A1 Range mm CS3...

Page 18: ...an Solar technical support department in writing for advice Tracker 1P Bolting method Install and tighten the module clamps to the mounting rails using the torque stated by the mounting hardware manuf...

Page 19: ...0 1800 600 80 2400 2400 Tracker 2P Bolting method Module type Mounting hole space mm Mounting hole location Plain washer outer diameter mm Test load Pa CS3W PB AG CS3W MB AG A1 A3 400 B1 B3 1155 B1 B2...

Page 20: ...tial electric shock hazard Cracked or broken modules represent an electric shock hazard due to leakage currents and the risk of shock is increased when modules are wet Before cleaning thoroughly inspe...

Page 21: ...S Method A Compressed Air Canadian Solar recommends cleaning the soft dirt like dust on modules just with air pressure This technique can be applied as long as the method is efficient enough consideri...

Page 22: ...93 25 CS3U 380MB AG 380 40 0 9 50 47 8 10 01 25 CS3U 385MB AG 385 40 2 9 58 48 0 10 09 25 CS3U 390MB AG 390 40 4 9 66 48 2 10 17 25 CS3U 395MB AG 395 40 6 9 73 48 4 10 25 25 CS3U 400MB AG 400 40 8 9 8...

Page 23: ...31 2 8 98 37 9 9 47 25 CS3K 285PB AG 285 31 4 9 08 38 1 9 56 25 CS3K 290PB AG 290 32 3 8 98 38 9 9 49 25 CS3K 295PB AG 295 32 5 9 08 39 1 9 57 25 CS3K 300PB AG 300 32 7 9 18 39 3 9 65 25 CS3K 305PB AG...

Page 24: ...9 11 71 25 CS3W 460MB AG 460 40 9 11 25 49 1 11 77 25 CS3W 465MB AG 465 41 1 11 32 49 3 11 83 25 CS3Y 465MB AG 465 43 6 10 67 52 3 11 42 25 2260 x 1048 x 32 89 0 x 41 3 x 1 26 in 29 9 65 9 lbs CS3Y 4...

Page 25: ...n Circuit Voltage Voc V Short Circuit Current Isc A Max Series Fuse Rating A Overall Dimension mm Weight Kg CS6W 530MB AG 530 40 9 12 96 48 8 13 80 30 CS6W 535MB AG 535 41 1 13 02 49 0 13 85 30 CS6W 5...

Page 26: ...019 Rev 1 3 is released in September 2019 Rev 1 4 is released in December 2019 Rev 1 4 is released in December 2019 Rev 1 5 is released in April 2020 Rev 1 6 is released in May 2020 Rev 1 7 is release...