DIP Switch Functions
Fixed-function DIP Switches
A1
Test Mode (normally Off).
A2
In “ON” position, add one high-speed pump (or blower) with Heater.
A3
In “OFF” position, add two high-speed pump with Heater.
A4
In “OFF position, add 4 high-speed pump with Heater.
A5
In “ON” position, enables Special Amperage Rule B. means heater
shuts off when pump is on high speed
A6
Persistent memory reset (Used when the spa is powering up to
restore factory settings as determined by software
configuration).
A7
in Off position 1 minute cool down fo relectric heating on for 5
minute cool down for gas heating
A8
in Off position not assigned
A9
in Off position not assigned
A10
in Off position not assigned
WARNING:
Setting DIP switches or jumpers incorrectly may cause abnormal
system behavior and/or damage to system components. Refer to Switchbank
illustration on Wiring Configuration page for correct settings for this system.
A2, A3 and A4
work in combination to determine the number of high-speed
devices and blowers that can run before the heat is disabled i.e A2 and A3 in
the ON position and A4 in the OFF position will allow the heater to operate with
up to 3 high-speed pumps (or two HS Pumps and Blower) running at the same
time. Heat is disabled when the fourth high-speed pump or blower is turned
on.
Note: A2/A3/A4 all off = No heat with any high or blower.
J31
Jumper on 1 pin with 2.0kW or smaller heater
Jumper on 2 pins with 3.0kW or higher heater