6 |
EN-Rev IM/GN-BM-EU/1.21 Copyright © July 2019. Canadian Solar Inc.
·
Do not
carry modules on your head.
·
Do no
t drop or place objects (such as tools) on the mo-
dules.
·
Do not
use sharp instruments on the modules.
·
Do not
leave modules unsupported or unsecured.
·
Do not
change the wiring of bypass diodes.
· Keep all electrical contacts clean and dry at all times.
PRODUCT IDENTIFICATION
· Each module has two identical barcodes (one in the
laminate under the front glass, the second on the rear
side of the module) that act as a unique identifier. Each
module has a unique serial number containing 14 di-
gits.
· A nameplate is also affixed to the rear glass of each
module. This nameplate specifies the model type, as
well as the main electrical and safety characteristics of
the module.
5.0 MODULE INSTALLATION
PRECAUTIONARY MEASURES AND
GENERAL SAFETY
· Prior to installing modules please obtain information
about any requirements and necessary approvals for
the site, installation and inspection from the relevant
authorities.
· Check applicable building codes to ensure that the con-
struction or structure (roof, facade, support, etc.) can
bear the module system load.
· Canadian Solar Inc. bifacial double glass solar modules
(BiKu and BiHiKu) have been qualified for Application
Class A (equivalent to Safety Class II requirements). Mo-
dules rated under this class should be used in systems
operating at voltage above 50V or power above 240W,
where general contact access is anticipated.
· Canadian Solar Inc. bifacial double glass modules have
been certified as Type 3 or Type 13 according to UL 1703
and as Class A for fire performance according to IEC
61730-2, please refer to the datasheet or the product
nameplate for the detailed types.
· Consult your local authority for guidelines and require-
ments for building or structural fire safety.
UL 1703 SYSTEM FIRE RATING REQUIREMENTS
· The fire rating of this module is only valid when the pro-
duct is installed as specified in the mechanical mounting
instructions.
· When installing the modules, ensure the assembly is
mounted over a fire resistant roof covering rated for the
application.
· A photovoltaic system composed of UL1703 certified mo-
dules mounted on a UL2703 certified mounting system
should be evaluated in combination with roof coverings
in accordance with UL1703 standard, with respect to mee-
ting the same fire classification as the roof assembly.
· Mounting systems with a System Fire Class Rating (Class
A, B or C), tested in conjunction with fire rated “Type 3” or
“Type 13” rated modules, are considered acceptable for
use with Canadian Solar Inc. modules, provided the moun-
ting system does not violate any other requirement of this
manual.
· Any mounting system limitation on inclination or accesso-
ry required to maintain a specific System Fire Class Rating
should be clearly specified in the installation instructions
and UL2703 certification of the mounting system supplier.
ENVIRONMENTAL CONDITIONS
· The module is intended for use in general open-air clima-
tes, as defined in IEC 60721-2-1: Classification of environ-
mental conditions Part 2-1: Environmental conditions ap-
pearing in nature - temperature and humidity.
· Please consult the Canadian Solar Inc. technical support
department for more information on the use of modules
in special climates, such as an altitude greater than
2000 m, heavy snow, severe hail storm, hurricane etc.
· Do not install modules near open flames or flammable
materials.