Camus ProtoNode Start-up Guide
Page 29 of 87
4.9 Power-Up ProtoNode
Check power requirements in the table below:
Power Requirement for ProtoNode External Gateway
Current Draw Type
ProtoNode Family
12VDC/AC
24VDC/AC
30VDC
FPC – N34 (Typical)
170mA
100mA
80mA
FPC – N34 (Maximum)
240mA
140mA
100mA
FPC – N35 (Typical)
210mA
130mA
90mA
FPC – N35 (Maximum)
250mA
170mA
110mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of
the host system. A safety margin of 25% is recommended.
Figure 16: Required Current Draw for the ProtoNode
Apply power to the ProtoNode as shown below in
. Ensure that the power supply used complies
with the specifications provided in
•
ProtoNode accepts either 9-30VDC or 12-24VAC on pins 4 and 5.
•
Frame GND should be connected.
Power to
ProtoNode
ProtoNode
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
Figure 17: Power Connections