Camtec ESB303 Quick Start Manual Download Page 2

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 
 

Technical Table 

Model 

ESB303.LED.200/400 

Peak Current Limiting ±6% 

48A 

R.M.S Current Limiting ±6% 

33,9A 

Maximum Allowed Capacitive Load  

6.000uF 

Limiting Time (T

on

 Power On)  

350ms (±50ms) 

Release Time (T

off

 Low Voltage) 

800ms (±50ms) 

Limiting Interval [T

interval 

for AC

cont.

≥ 1200ms 

Circuit breaker at 30°C 

We suggest using a B13A or a B16A MCB with 10kA (never use an MCB >16A) 

AC Input Range 

184-265Vac to power the device between N (neutral) and the conductors L1, L2, L3 

AC Nominal Input Range 

200-240Vac to power the device 

L1, L2, L3 conductor continuous capability 

400Vac 16A between the conductors L1, L2, L3 

Line Frequency 

16 ⅓ Hz – 440Hz 

Switch-On Voltage 

165Vac 

AC Lower Margin 

52Vac (AC dump / drop out voltage) 

AC Current 

16A continuous load current at the inputs and at the outputs 

Power Supply 

No external power supply required, item is self-powering 

Power Consumption 

<3.1W constant at continuous operation, <1.1W per phase conductor 

Limiting Cycles 

Between each limiting action shall be a break of 20 sec., to let the device cool down until the next 
limiting starts 

Internal Protection 

Thermal fuse protects from overheat & fire  

Cooling 

Natural convection 

Operation Temp. 

Ambient temperature -40°C ... +60°C continuous  
(see operations temperature list for details in this manual) 

Storage Temp. 

-40°C ... +85°C for 2 years 

EMI 

EN55032 class B 

EMS 

EN61000-6-2,3 

Safety Norms 

EN60950-1, EN61010-1:2011-07, VDE 0411-1:2011-07

 

Safety Class II 

VDE0805, VDE0100/ÖVE8001 

ROHS conformity 

ROHS Directive 2011/65/EU, (EU)2015/863 

REACH conformity 

REACH Directive 1907/2006 

MTBF Calculation 

460.000h (IEC/EN61709, Siemens SN29500) 

MTTF Calculation 

415.000h (+30°C) (IEC/EN61709, Siemens SN29500) 

Humidity 

95% (+25°C) not condensing 

Pollution Degree 

2 (IEC/EN50178) 

Environmental 

Thermal environment 3K3, mechanics 3M4 (IEC/EN60721) 

Altitude max. 

4000m (13123 ft.) above sea level 

Dimensions (WxHxD) 

(Wide=5TE), 97.8x110x62mm 

Housing Parameters 

UL94V-0 ABS RTI 85°C, housing for DIN/VDE0603 cutout box and for wall mount 

DIN-Rail 

DIN-Rail TS35mm DIN/EN60715 (TS35/7,5 und TS35/15) 

Weight 

300g / 0,66lb 

Connections 

Spring-type terminal with cable protection 0,5...6mm² 21…10AWG according with IEC/EN60664-1, 
IEC/EN61984 
Use copper conductors only. Tightening torque per terminal block is 0.5 - 0.6 Nm / 4.5 - 5.3 lbf-in 

 

General Description  

The CAMTEC ESB303 is the 3rd generation and cost-effective inrush current limiter. The limiter is designed for 200-240V 
and can be operated in a 3x400Vac 16A networks with a neutral conductor. The ESB303 can either be used as 3-channel 
single-phase ESB or as a 3x400Vac ESB. Each phase connection allows to connect 6000uF capacitive load. It is necessary 
to connect the Neutral conductor to the ESB to let the device operate. The PE conductor must not be connected to the 
ESB303.  The  line  frequency  range  is  16⅓Hz  –  440Hz.  The  ESB303-Limiter  shall  be  located  between  the  line-
switcher/contactor  and  the  load.  The  ESB-models  are  designed  for  capacitive  loads  (not  for  inductive  loads  like 
coils/transformers, not for AC-motors and not for DC-voltage application). In the moment of switching-on the system 
the inrush current of the installed load will be limited for the defined time T

on 

. Independent from the previous inrush 

level; the current limiting is always strict. After T

on

 elapses the current limiting circuit of the ESB303 will be bypassed. 

Then the load is directly connected to the AC. The electrical network can be stressed with current loads as normal (e.g. 
motors, pumps). If an AC dump overshoots the defined time T

off

, it will be detected by the ESB303. As soon as the AC 

recovers the inrush will be  limited, again. The  ESB303-models provide an internal temperature control. In case of a 
failure the device shuts down to safely prevent from overheating or fire. The power consumption of the unit is <3,3W 
(<3x1,1W per phase conductor at 230Vac) 

 

Verkoopadres:

 Advantec Electronics

, Industrieweg 10 G, 4731 SC Oudenbosch, Nederland, Tel: (31) 085 87 688 37  

Website: www.advantecelectronics.nl, Email: [email protected] 

Summary of Contents for ESB303

Page 1: ...ture protection IP20 UL94V 0 housing DIN43880 for DIN VDE0603 cutout box The ESB303 is a budget priced inrush peak current limiter for high loads in LED applications complex automation systems and in the machine building The ESB303 offers effective and interference free operation with capacitive loads It is simple to integrate into existing equipment The ESB303 is self powering and does not requir...

Page 2: ...ironmental Thermal environment 3K3 mechanics 3M4 IEC EN60721 Altitude max 4000m 13123 ft above sea level Dimensions WxHxD Wide 5TE 97 8x110x62mm Housing Parameters UL94V 0 ABS RTI 85 C housing for DIN VDE0603 cutout box and for wall mount DIN Rail DIN Rail TS35mm DIN EN60715 TS35 7 5 und TS35 15 Weight 300g 0 66lb Connections Spring type terminal with cable protection 0 5 6mm 21 10AWG according wi...

Page 3: ...n phase conductor and the neutral Each phase connection is limited separately thus a loss or a breakdown of each line is protected by the ESB303 unit The figure 1 1 shows the distribution of the potentials in relation to the neutral connection In three phase systems the effective value of the sinusoidal AC mains voltage between an outer conductor and the neutral conductor is 230V and between two o...

Page 4: ... to exceed it in a 16A network Installed contractors will be discharged and their lifetimes will considerable increase Note that the ESB303 is not designed to operate together with gas induction lamps or other conventional lighting device The ESB303 is designed for capacitive loads only Design In of the ESB303 into A C networks The ESB303 model is a precise inrush current limiter with an overall t...

Page 5: ... and the next active or temperature sensitive device shall be 17 5mm To a non active device the distance can be 0mm The power consumption of the device is 3 3W 3x1 1W per phase conductor constant at 230Vac continuous operation Make sure that the ventilation holes below and above the unit are not blocked to allow free air convection The neutral must be connected to the device If the neutral is not ...

Page 6: ... este manual como referencia para futuras consultas La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cualificado Por favor lea detenidamente este manual antes de conectar la fuente de alimentación Si se produce un fallo o mal funcionamiento durante la operación desconecte inmediatamente la tensión de alimentación En ambos casos el equipo debe ser inspeccio...