Shutdown 

All CPS-EC units are featured with an external shutdown (open collector).  
The power supply operates when the connection is open. When the  
connection is closed the power supply goes into a standby mode  
(short circuited). The power supply powers up as soon as the shutdown 
connections is opened. The signal through the connections is 1Vdc max. . The 
shutdown connections have an internal pull-up resistor with 4700 

Ω

 at the plus 

line (max. +12V inserted). 

 

DC-OK (Power Good Relay) 

The DC ok relay indicates if the output voltage is low and if the AC voltage is low. 
The contact is galvanic insulated to the AC input and the DC output connections. 
The isolation is 3000Vac with a forced isolation and covers the overall adjustment 
range of the CPS-EC series up to 400Vdc. If the DC voltage is ok the relay is 
closed, if the power supply unit is in false operation, in the shutdown or in the 
inhibit mode, the relay is open. Considering the lower and the upper margin of the 
AC voltage detection it is to say that the CPS-EC series starts at 80Vac/150Vac 
depending on the AC input selector. The unit starts with 210Vdc when a DC 
voltage applies to the input. Make sure to set the AC input selector to 230Vac 
(factory setting) for DC input supply. 
The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK 
Relay indicates a low voltage. The nominal voltage of the cell voltage of a typical lead acid battery VRLA & 
vented GEL & AGM is listed (OPsZ, OPzS, OPzV, OGi, OGiV, GiV types). 

WARNING!

 

Regarding the DC-output voltage setting range it is important to consider that this data sheet 

shows the guaranteed values. In practise the range will be wider and with some models the lower margin of 
the setting range will be below the DC ok high margin of the DC-ok relay. Make sure that the output voltage 
setting will properly stay above the DC ok high margin to avoid false messages from the relay.  

Hysteresis & Threshold Margins 

Model 

Nominal [V] 

DC ok low 

DC ok 
high 

No. of Cells 

Nominal Cell [V] 

Input ok low 

Input ok high 

CPS-EC480.024 

24V 

21,5Vdc 

22,8Vdc 

12 

26,76 – 28,80Vdc 

75Vac 
140Vac 
175Vdc 

80Vac 
150Vac 
210Vdc 
 
(the power 
supply unit starts 
at 
80Vac/150Vac/21
0Vdc) 

CPS-EC480.036 

36V 

32,4Vdc 

34,2Vdc 

18 

40,14 – 43,20Vdc 

CPS-EC480.048 

48V 

43,2Vdc 

45,6Vdc 

24 

53,52 – 57,60Vdc 

CPS-EC480.060 

60V 

54,0Vdc 

57,0Vdc 

30 

66,90 – 72,00Vdc 

CPS-EC480.072 

72V 

64,8Vdc 

68,4Vdc 

36 

80,28 – 86,40Vdc 

CPS-EC480.110 

110V 

99,0Vdc 

104,5Vdc 

54 

120,42 – 129,60Vdc 

CPS-EC480.150 

150V 

118,8Vdc 

125,4Vdc 

CPS-EC480.220 

220V 

198,0Vdc 

209,0Vdc 

108 

240,84 – 259,20Vdc 

CPS-EC480.300 

300V 

237,6Vdc 

250,8Vdc 

150 

334,50 – 360,00Vdc 

DC OK Indication 

Power Supply Status 

Normal 

Low [V] 

Over Temperature 

Shut Down Closed 

Inhibit Open 

Relay Operation status 

Closed 

Open 

Open 

Open 

Open 

 

LED Signal Indication 

LED 

Low [V] 

Over [V] 

Over Temp. 

Inhibit Open 

Shut Down 

Constant [V] 

Constant [C] 

CV 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

CC 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

OT 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

SD/INH 

OFF 

OFF 

OFF 

ON 

ON 

OFF 

OFF 

 

 

 

 

+12V 

Summary of Contents for 3041105001CA

Page 1: ...l 1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 30ms Soft start auto recovery High reliability shock vibration proof EMC meets CE norm class B Overload and short circuit protection Large terminals 4x AWG22...

Page 2: ...d with a 15 turns high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of...

Page 3: ... to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 320ms Start up from Inhibit Typ 32...

Page 4: ...tput Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation for the 300Vdc DC Voltage Current adjustment range Rated DC Voltage 24Vdc 36Vdc 48Vdc...

Page 5: ...WARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires I...

Page 6: ...y setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltage of a typical lead acid battery VRLA vented GEL AGM is listed OPsZ OPzS OPzV OGi OGiV GiV types WARNING Regarding the DC output voltage setting range it is important to consider that this data shee...

Page 7: ... 48 21 0 1008W CPS EC1000 060 75 13 3 60 16 7 1008W CPS EC1000 072 90 11 1 72 13 9 1008W CPS EC1000 110 137 5 7 3 110 9 1 1008W CPS EC1000 150 180 5 6 150 6 7 1008W CPS EC1000 220 264 3 8 220 4 5 1008W CPS EC1000 300 360 2 8 300 3 33 1008W Inrush Current Limiter The unit is featured with an electronic inrush current limiter ex 230Vac 9 8Arms 13 8Apeak The built in circuit is a very precise limiter...

Page 8: ...plies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Option We offer the CPS EC series with an optional coating It is to be used in e g dusty dirty high humidity area or in awaiting quick temperature changes Short circuit and corrosion at print board lines ...

Page 9: ...t in injury or death Mechanics Mechanics Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN6027...

Page 10: ... and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1000 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to inst...

Page 11: ... 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14...

Page 12: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A for 230Vac and 32A for 115Vac It is prohibited to use the unit witho...

Reviews: