CPS-EC1000(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.1/12 (03.2022.00.0)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

CPS-EC1000

 

1008W Precision DC Rectifier

 

DIN-Rail Battery Charger, C/V Adjustable Industrial Power  
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Specification: 

 

Real time output current monitoring 

 

Precision potentiometer f. voltage & current 

 

Power Good Relay AC & DC-ok 

 

C/V curve down to 0V, no foldback 

 

Sense control 1V per load line 

 

Electronic inrush current limiter 13.8Apeak 

 

Inhibit function (Interlock) 

 

External shutdown 

 

Efficiency up to 92% 

 
 

 

Precise dynamic response to load change 

 

Designed for long life under full stress 

 

Strong input filters 

 

Hold up time >30ms 

 

Soft start & auto-recovery 

 

High reliability, shock & vibration proof  

 

EMC meets CE norm class B 

 

Overload and short circuit protection  

 

Large terminals 4x AWG22 – AWG6 (0,5 – 16mm²) 
 

Models 

Voltage 

Voltage setting 

Current setting 

CPS-EC1000.024 

24Vdc 

24 – 30Vdc 

21 – 44,1A 

CPS-EC1000.036 

36Vdc 

36 – 45Vdc 

14 – 29,4A 

CPS-EC1000.048 

48Vdc 

48 – 58Vdc 

10,5 – 22A 

CPS-EC1000.060 

60Vdc 

60 – 75Vdc 

8,4 – 17,6A 

CPS-EC1000.072 

72Vdc 

72 – 90Vdc 

7,0 – 14,6A 

CPS-EC1000.110 

110Vdc 

110 – 137,5Vdc 

4,6 – 9,6A 

CPS-EC1000.150 

150Vdc 

132 – 180Vdc 

3,4 – 7A 

CPS-EC1000.220 

220Vdc 

220 – 264Vdc 

2,3 – 4,8A 

CPS-EC1000.300 

300Vdc 

264 – 360Vdc 

1,7 – 3,5A 

 

 

 

 

 

Summary of Contents for 3041105001CA

Page 1: ...l 1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 30ms Soft start auto recovery High reliability shock vibration proof EMC meets CE norm class B Overload and short circuit protection Large terminals 4x AWG22...

Page 2: ...d with a 15 turns high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of...

Page 3: ... to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 320ms Start up from Inhibit Typ 32...

Page 4: ...tput Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation for the 300Vdc DC Voltage Current adjustment range Rated DC Voltage 24Vdc 36Vdc 48Vdc...

Page 5: ...WARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires I...

Page 6: ...y setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltage of a typical lead acid battery VRLA vented GEL AGM is listed OPsZ OPzS OPzV OGi OGiV GiV types WARNING Regarding the DC output voltage setting range it is important to consider that this data shee...

Page 7: ... 48 21 0 1008W CPS EC1000 060 75 13 3 60 16 7 1008W CPS EC1000 072 90 11 1 72 13 9 1008W CPS EC1000 110 137 5 7 3 110 9 1 1008W CPS EC1000 150 180 5 6 150 6 7 1008W CPS EC1000 220 264 3 8 220 4 5 1008W CPS EC1000 300 360 2 8 300 3 33 1008W Inrush Current Limiter The unit is featured with an electronic inrush current limiter ex 230Vac 9 8Arms 13 8Apeak The built in circuit is a very precise limiter...

Page 8: ...plies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Option We offer the CPS EC series with an optional coating It is to be used in e g dusty dirty high humidity area or in awaiting quick temperature changes Short circuit and corrosion at print board lines ...

Page 9: ...t in injury or death Mechanics Mechanics Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN6027...

Page 10: ... and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1000 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to inst...

Page 11: ... 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14...

Page 12: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A for 230Vac and 32A for 115Vac It is prohibited to use the unit witho...