4.1 Wiring
4.1.1 SDM-CD16ACA power and control connections
Refer to
(p. 3) and
(p. 5) for SDM-CD16ACA operating power and control
connections to the data logger.
Table 4-1: Data logger to SDM-CD16ACA connections (see caution)
Connection Order
SDM-CD16ACA
Data Logger
(see notes)
Function
First
12V
12 V on data logger or
External supply
Power
Second
G
Gnd
Common ground
C1
SDM-C1 (CR3000) or
C1 (other data loggers)
Data
C2
SDM-C2 (CR3000) or
C2 (other data loggers)
Clock
C3
SDM-C3 (CR3000) or
C3 (other data loggers)
Enable
CAUTION:
The order in which connections are made is critical. Always connect 12 V first, followed by
ground, then Control Ports.
NOTE:
The CR6 allows SDM operation through terminals C1, C2, and C3 as shown in
In addition, the U terminals on the CR6 may be used in the same manner. U1–U3, U5–U8, and
U9–U11 are usable in the same Data, Clock, Enable order as the C terminals.
4.1.2 Controlled device to SDM-CD16ACA connections
DANGER:
ELECTROCUTION HAZARD! USE EXTREME CAUTION WHEN WORKING WITH HIGH
VOLTAGE INPUTS. DO NOT COME IN CONTACT WITH HOT LEADS!
(p. 6) shows how the switches in each channel operate. NO means “normally open”,
NC means “normally closed”. COM means “common” to NO and NC.
SDM-CD16ACA 16 Channel AC/DC Controller
5