SDM-CD16AC 16 Channel AC/DC Controller
Input Location assignments are as follows:
Input
Location
Location
Label
Description
1..5
Temp #1..#5
Avg temp, greenhouse 1..5
10..14
Heat #1..#5
Heater control, greenhouse 1..5 SDM-CD16AC
Port 1..5
15..19
Cool #1..#5
Cooler control, greenhouse 1..5 SDM-CD16AC
Port 6..10
20..24
Fan #1..#5
Fan control, greenhouse 1..5 SDM-CD16AC
Port 11..15
1: Beginning of Loop (P87)
Master Loop, End
1: 0
Delay
Loop at Step 30
2: 5
Loop
Count
START HEATER CONTROL LOGIC
2: If X<=>F (P89)
If "Heater On"
1: 1--
X
Loc
threshold is
2: 4
<
exceeded
3: 23.5
F
4: 30
Then
Do
Then
3: Z=F (P30)
Put a "1" into Heater
1: 1
F
Control Location
2: 0
Exponent of 10
3: 10--
Z Loc :
4: End (P95)
End Then Do/End
5: If X<=>F (P89)
If Heater
1: 10--
X
Loc
#1 on (Heater Control
2: 2
<>
Location <> 0)
3: 0
F
4: 30
Then
Do
Then
6: If X<=>F (P89)
1: 1--
X
Loc
Temp #1 Check Upper Threshold
2: 3
>=
to see if heater should
3: 25.5
F
be turned off
4: 30
Then
Do
7: Z=F (P30)
If heater should be turned
1: 0
F
off, enter a "0" into
2: 0
Exponent of 10
heater control location
3: 10--
Z Loc :
8: End (P95)
Else Then Do/End
12