SC932C 9-PIN TO RS232-DCE INTERFACE

The SC932C is used to interface a Campbell Scientific datalogger to modem devices that are configured
with an RS232 DCE (Data Communications Equipment) serial port.  The most common application is to
allow the connection of a RAD short haul modem or third party telephone modem to a datalogger.

The SC932C has the following features:

 

Generates true RS232 signal levels to the DCE device, resulting in good noise immunity.

 

Powered from the 5V supply of the datalogger, which is also available to provide power to the DCE,
if required for line-powered modems.

 

Generates the required ring signal to wake up the datalogger, either when characters are received
or when there is a ring signal from the DCE.

 

Allows simultaneous connection of synchronous devices (e.g., Storage Modules) to the datalogger.

 

Provides a mechanism for the datalogger to control the line state of intelligent modems via DTR
handshaking control.

 

Convenient ‘jumperless’ design.

1.  INSTALLATION

Use the SC12 ribbon cable (provided) to
connect the datalogger’s 9-pin CS I/O port to
the 9-pin connector on the SC932C.  The
SC932C can usually be connected to the
RS232 device by plugging the SC932C directly
into the serial connector on the RS232 device.
No further configuration is normally required.

A typical application with a RAD modem would
comprise:

SC932C

FIGURE 1.  SC932C Connected to RAD

Short-Haul Modem

If the RS232 device does not have a suitable
25-pin ‘D’ socket, you may need an adaptor
cable (see Appendix A).

2.  USE WITH INTELLIGENT

TELEPHONE MODEMS

If an ‘intelligent’ telephone modem is being
used, configure it to allow the SC932C to
control its line status via the DTR line.  This can

prevent the modem staying on-line
unnecessarily, which can lead to excessive
telephone charges and also delay reconnection
to the datalogger.

Most phone modems can be configured to
respond to the DTR line, although this is not
always the default setting.  Although this feature
is sometimes controlled by a hardware
configuration switch, more often it is a software
setting, e.g. AT&D2&W is the command for a
Hayes-compatible modem to force the modem
to follow the DTR status.

3.  OTHER APPLICATIONS

The SC932C can be used in more specialized
applications.  Appendix B gives installation
details where even lower power consumption
may be possible, and also for applications
where higher power outputs for the RS232
device are required.

Summary of Contents for SC932C

Page 1: ...INSTRUCTION MANUAL SC932C 9 Pin to RS 232 DCE Interface Revision 6 97 C o p y r i g h t c 1 9 9 7 C a m p b e l l S c i e n t i f i c I n c...

Page 2: ...all other warranties expressed or implied including warranties of merchantability or fitness for a particular purpose CAMPBELL SCIENTIFIC INC is not liable for special indirect incidental or consequen...

Page 3: ...DCE Interface A 1 A 2 Cable for Connection to a 9 Pin DCE Interface A 1 B Technical Details of Special Modes of Operation B 1 B 1 Power Modes B 1 B 2 Handshaking Lines B 1 B 3 Printer Only Output B 1...

Page 4: ...This is a blank page...

Page 5: ...C The SC932C can usually be connected to the RS232 device by plugging the SC932C directly into the serial connector on the RS232 device No further configuration is normally required A typical applicat...

Page 6: ...This is a blank page...

Page 7: ...SC932C to 25 pin DCE Interface NOTE The link between pins 4 and 4 marked with the may not be required see the section on low power operation in Appendix B A 2 CABLE FOR CONNECTION TO A 9 PIN DCE INTER...

Page 8: ...This is a blank page...

Page 9: ...s which do not need to source power from the SC932C This is done by not connecting pin 11 or the RTS line to the RS232 device This is because a small current will flow from the active RTS line into a...

Page 10: ...ves communications mode ME goes low there is a delay of approximately one second before serial or ring line activity from the RS232 device will re awaken the datalogger This prevents spurious messages...

Page 11: ...With 3 inputs connected DTR RTS and Tx from the SC932C of the minimum 3k input impedance and high communications activity the consumption may be up to 16mA RS232 OUTPUT LEVELS RTS 4 2 4 5V with 3k loa...

Page 12: ...active by SC932C 7 GND Signal Ground 11 in PWR If held 3 5V will force SC932C into high power mode 20 out DTR Held high if ME is high see Appendix B TABLE C 2 9 Pin Male Connector Pin out Pin No I O N...

Page 13: ...This is a blank page...

Page 14: ...campbellsci com br suporte campbellsci com br Campbell Scientific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientifi...

Reviews: