Appendix L. RF400/RF410 Average Current Drain Calculations
L-3
EXAMPLE #1
(Remote RF400/RF410 in default standby mode)
There is a Point-to-Point system with base RF400/RF410 and remote
RF400/RF410. The
remote
station senses weather conditions and sends low-
resolution data to final storage. The base station collects 10 data points from
the remote station once per minute. Both stations are configured for “<4 mA,
½ sec Cycle” (the default standby mode). The remote station operates on solar
power and we are interested in knowing the average current drain contribution
of the RF400/RF410. From the above section:
It = Is + Id + Ir + Ii
Calculating each term:
Is = table mA value = 4 mA
It
≈
6.1 mA
The dominant average current drain contributors are the standby mode current
and the “time of inactivity to sleep” currents. If large quantities of data per
minute were being generated/collected, then Id would become a significant
contributor. In this example the “time of inactivity to sleep” could be reduced
because only 10 data points are sent per collection. Try a value of 10 instead
of 50 reducing the Ii contribution from 2 mA to 0.4 mA.
mA
0.08
mA
73
ms
60,000
ms
65
mA
73
(ms)
T
(ms)]
N
2
(ms)
45
[
Id
=
×
=
×
+
=
mA
0.008
mA
24
(ms)
60,000
(ms)
20
Ir
=
×
=
mA
2
mA
24
(ms)
60,000
ms
5000
Ii
=
×
=
Summary of Contents for RF400
Page 4: ...This is a blank page...
Page 8: ...RF400 Table of Contents iv This is a blank page...
Page 40: ...This is a blank page...
Page 44: ...Appendix B Setup Menu B 4 This is a blank page...
Page 54: ...This is a blank page...
Page 64: ...Appendix H Distance vs Antenna Gain Terrain and Other Factors H 8 This is a blank page...
Page 72: ...Appendix J Monitor CSAT3 via RF400 Series J 2 This is a blank page...
Page 88: ...Appendix L RF400 RF410 Average Current Drain Calculations L 10 This is a blank page...
Page 89: ...This is a blank page...