CS505 FUEL MOISTURE SENSOR
6
9: Polynomial (P55)
Convert period to percent moisture content.
1:
1
Reps
2:
2
X Loc [ CS505mSec ]
3:
3
F(X) Loc [ fuelmoist ]
4:
-220.14
C0
5:
365.89
C1
6:
-114.96
C2
7:
0.0
C3
8:
0.0
C4
9:
0.0
C5
10: Do (P86)
Set flag 1 low
1:
21
Set Flag 1 Low
11: End (P95)
End
*Table 2 Program
02:
0.0000
Execution Interval (seconds)
*Table 3 Subroutines
End Program
-Input Locations-
1 CS505kHz 1 1 1
2 CS505mSec 1 1 1
3 fuelmoist 1 0 1
6. MAINTENANCE
The sensor element should be changed at least
once a year with a new element in the spring.
Since the characteristics of wood change so
rapidly, more frequent replacements may be
desirable.
To change the sensor element, loosen the
Phillips head screws and replace with the new
element. Tighten the screws after replacing the
element.