C-1
Appendix C. SDI-12 Commands/
Changing Settings
The SDI-12 commands are entered using the 25616,
Adjustment/Display
Module
, or the terminal emulator in
LoggerNet
or
PC400
(see Appendix
Using Terminal Emulator and a Datalogger to Send Commands
(p. C-9)
). These
commands are also used in CRBasic or Edlog programming (see Section
(p. 14)
SDI-12 commands have three components:
•
Sensor address (a)
– a single ASCII character, and is the first
character of the command. The sensor address allows multiple sensors
to be connected to a single control port. The default address is zero,
and typically is only changed when multiple sensors are connected to
the same port. Valid addresses are 1 to 9, A to Z, or a to z.
•
Command body (e.g., M1)
– an upper case letter (the “command”)
followed by alphanumeric qualifiers.
•
Command termination (!)
– an exclamation mark.
An active sensor responds to each command. Responses have several standard
forms and terminate with <CR><LF> (carriage return – line feed). SDI-12
commands supported by the radar sensors are listed in TABLE
TABLE C-1. SDI-12 Commands
Function
SDI-12 Command
Address Query
?!
Send Identification
aI!
Acknowledge Active
a!
Change Address
aAb!
Where a is the current address and b is the
new address.
Start Verification
aV!
Start Measurement
aM!
Start Measurement and Request
CRC
aMC!
Send Data
aD0!...aD9!
Additional Measurements
aM1!...aM9!
Additional Measurement and
Request CRC
aMC1!...aMC9!
Start Concurrent Measurement
aC!