Section 10. Troubleshooting
488
•
Check for a loose ground wire on a sensor powered from 12V.
•
If a volt meter is not available, disconnect any sensor that is powered
from a 12V source to see if the measurements come back to normal. If
multiple sensors are power by 12V, disconnect one at a time.
10.14 Troubleshooting — Rebooting
Following are ways to reboot the CR800. Rebooting should be a last resort.
Regardless of the method used to reboot, try to collect data from the CR800
before rebooting as there is a good chance data will be lost during the process. If
you can connect using
DevConfig
, try to save CR800 settings.
•
Reboot manually in
terminal mode
(p. 483):
> REBOOT
•
Reboot under program control with
Restart
instruction:
Reboot under program control with
Restart
instruction
Public
Reboot
BeginProg
Scan
()
If
Reboot
Then
Reboot = false
Restart
EndIf
NextScan
EndProg
•
Reboot under program control with
FileManage()
instruction:
Reboot under program control with
FileManage()
instruction:
Public
Reboot
BeginProg
Scan
()
If
Reboot
Then
Reboot = false
FileManage
("Status.ProgName",6)
EndIf
NextScan
EndProg
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......