Section 8. Operation
378
and flow meters, are calibrated in terms of frequency (
Hz
(p. 501)
) so are
usually measured using the
PulseCount()
frequency-output option.
•
Accuracy of
PulseCount()
is limited by a small scan-interval error of
±(3 ppm of scan in 10 µs), plus the measurement resolution error
of ±1 / (scan interval). The sum is essentially ±1 / (scan interval).
•
Use the
LLAC4
(p. 562)
module to convert non-TTL-level signals,
including low-level ac signals, to TTL levels for input into
C
terminals.
•
As shown in the table
Switch Closures and Open Collectors
(p. 378),
C
terminals, with regard to the 6.2 V Zener diode, have an input resistance
of 100 kΩ with input voltages < 6.2 Vdc. For input voltages ≥ 6.2 Vdc,
C
terminals have an input resistance of only 220 Ω.
Switch Closures and Open Collectors on P Terminals
Switch Closure on
P
Terminal
Open Collector on on
P
Terminal
Switch Closures and Open Collectors
Switch Closure on
C
Terminal:
No Pull-Up
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......